background image

Table 11 (below) and Table 10 (p. 25) illustrate the Series 935A alarm features.

Table 11 - Alarm Functions

SET

Latching alarm

Silence alarm

With this selection, an alarm
cannot be silenced at the 935A
front panel (unless the alarm
is latched [

[~LAt]

=

[yes]

],

and the alarm condition
no longer exists).

SET

A value from input Range Low to

[`AhI]

.

A value from

[`alo]

to input Range High

Alarm Low

Alarm High

An unlatched alarm self-clears
when actual temperature returns
to within the safe area.

At the Range Low value, a

,

press

displays

[`off]

and

[`ahi]

disables.

At the Range High value, a

.

press

displays

[`off]

and

[`ahi]

disables.

[`lat]

[`sIl]

[`alO]

[`ahI]

[``no]

[``no]

[`yes]

[`yes]

A latched alarm requires the
operator to press the

ß

key to clear after the actual
temperature returns to within
the safe area.

With this selection, an alarm
can be silenced by pressing the

ß

key.

[yes]

provides automatic

alarm silencing on start up.

Watlow Series 935A User’s Manual