beautypg.com

Error code actions, Error codes – Watlow Series 734 Program User Manual

Page 14

background image

Alarms & Error Codes, Chapter 5

14

WATLOW Series 733/734 Program Manual

Error Codes

Problem

Probable Cause

Solution

Er10 -
Stack overflow error

Er11 -
Zone 1 open sensor error

Er12 -
Zone 1 shorted sensor

Er13 -
Zone 2 Open sensor

Er14 -
Zone 2 shorted sensor

Er15 -
Zone 1 loop error

Er16 -
Zone 2 loop error

Microprocessor error

Open sensor

• Incorrect sensor type
• Measuring temperature

outside the sensor
range

Open sensor

• Incorrect sensor type
• Measuring temperature

outside the sensor
range

• Reversed sensor leads

• Faulty heater or gas

valve

• Shorted sensor
• Faulty output switching

device

• Blown fuse to heater
• Incorrect Pb1 value

for thermal system

See Er15 Probable
Cause above.
• Incorrect Pb2 value for

thermal system

• Cycle power

• Check the InP1 para-

meter. Verify it
matches your sensor.

• Check the InP1 para-

meter. Verify it
matches your sensor.

• Check the InP2 para-

meter. Verify it
matches your sensor.

• Check the InP2 para-

meter. Verify it
matches your sensor.

• Check heater or gas

valve

• Check sensor
• Check output switching

device

• Check fuse to heater
• Auto-tune the control

See Er15 Solution above.
• Auto-tune the control

˜

NOTE:
For Er10 through
Er14, first check
the sensor and
connections for a
reversed or open
sensor before
trying the solution
listed.

˜

NOTE:
Er06 through Er09,
and Er11 through
Er14 are self
clearing errors if
the condition that
caused the alarm
has been taken
care of.

Table 2 -
Continued

Error Code Actions

• Error codes will result in these conditons:

• The alarm outputs are in their alarm state (de-energized).
• The display alternately flashes the process value and error code.

• All keys are inactive except for the Temperature key

. This key snoozes the

error code and display for 30 seconds.

• The above conditions occur regardless of the LOC value, or the presence of the

Setup, Service or Calibration Menus.

• To clear a corrected error…

• Cycle power to the control.

OR

• Enter the Program mode by pressing the

keys simultaneously for

3 seconds.

• Press the Menu 12 key

12

once.

• Press the Time key

. The EC (Error Clear) prompt is displayed.

• Press the Temperature key

, and the error is cleared. Press the Time key

twice, and you're back to the Operation mode

[0)º0]

.

This manual is related to the following products: