Alarms & Error Codes, Chapter 5

WATLOW Series 733/734 Program Manual

13

Error Codes

ç

WARNING:
Electrical noise or a
noise event, excess
environmental
moisture or tem-
perature, or vibra-
tion may cause
Series 733/734
errors to occur. If
the cause of an
error is not other-
wise apparent,
check for these.

Table 2 -
Error Code
Troubleshooting

˜

NOTE:
For Er06 through
Er09, always check
the sensor and
connections for a
reversed or open
sensor before
trying the solution
listed.

Er01 -
ROM (Read Only
Memory) checksum error

Er02 -
RAM (Random Access
Memory) checksum error

Er03 -
Ambient sensor error

Er04 -
Configuration error

Er05 -
EEprom error

Er06 -
Zone 1 A/D (Analog to
Digital Converter) Under-
flow error

Er07 -
Zone 1 A/D overflow error

Er08 -
Zone 2 A/D (Analog to
Digital Converter) Under-
flow error

Er09 -
Zone 2 A/D overflow error

Problem

Probable Cause

Internal ROM is
defective.

Internal RAM is defective.

Ambient temperature is
below 32°F/0°C
Factory calibration
parameters have been
altered.

Defective microprocessor

Power loss while storing
data.

• Incorrect sensor type
• Measuring temperature

outside the sensor
range

• Reversed sensor leads

Open sensor

• Incorrect sensor type
• Measuring temperature

outside the sensor
range

Open sensor

Solution

• Cycle power

• Cycle power

• Check ambient tem-

perature at the control.

• Restore factory

calibration parameters.
See Calibration section.

• Cycle power

• Cycle power

• Check the InP1 para-

meter. Verify it
matches your sensor.

• Check the InP1 para-

meter. Verify it
matches your sensor.

• Check the InP2 para-

meter. Verify it
matches your sensor.

• Check the InP2 para-

meter. Verify it
matches your sensor.

To mask an alarm …
• When the SIL parameter is ON…

• Press the Temperature key

. This masks or "snoozes" the alarm message

for 30 seconds, and energizes the alarm output relay.

• When the SIL parameter is OFF…

• Press the Temperature key

. This masks or "snoozes" the alarm message

for 30 seconds, but does not energize the alarm relay.

Error Code Messages

The error code is visible in the display and alternates with the current display at a
3 second rate. The list below outlines the standard error codes associated with
the Series 733/734. They are designed to isolate specific problem areas and aid
in troubleshooting your control. If the problem persists, consult the factory.

This manual is related to the following products: