beautypg.com

55 rtd general parameter chart, Chart 4 – Watlow Series 1500 User Manual

Page 55

background image

Technical Reference

Use this chart to determine parameter

ranges, limits and default

settings. Then enter your setting for each

parameter. Make a photocopy of the chart and enter values for each program you use.

Program #

System

Programmer

Date

Series 1500 DIP Switch Settings

.

Sw-Position

Function

Setting

#1 -ON

Event Output #4 for both Ch-1 and Ch-2 are alarm outputs.

#1 - OFF

Event Output

#4

for both Ch-1 and Ch-2 are event outputs.

##2 - ON

Alarms are latching (displayed until cleared manually).

#2 - OFF

Alarms are non-latching (displayed only as tong as alarm condition exists).

I

#3-ON

The Ch-2 sensor is an RTD sensor. On the (A007-1316)

board,

Jumper J149 must be on Wl51, Jumper J152 must be on W153.

#3-OFF

The Ch-2 input is a 0-5V signal for 0-l 00% RH. On the (A007-1316) board,

Jumper J149 must be on W150, Jumper J152 must be on Wl54.

#4-ON

Dual PID

#4 - OFF

Single PID

#5 - ON

1

Factory use only. Must be in the ON position.

#6 - ON

Cold Start on power-up. (Memory cleared, parameters set to default values)

I

#6 - OFF

Warm Start on power-up. (Programmed values are retained for all parameters):

#7-ON °C function after a Cold Start.

#7

-

OFF

° F function after a Cold Start.

# & O F F

Not Used. Set in the OFF position

OFF

RTD Series 1500 Parameter Ranges

Prompt

Parameter

Number of Steps

Step Type (Data Comm.)

S1

Ch-1 Set Point

S

2

Ch-2 Set Point

Fl

.

ON (DIP 1 ON) Dec. Equiv
ON (DIP 1=ON) Dec. Equiv.

E2

El

ON (DIP 1=OFF) Dec. Equiv.

E2

ON (DIP l=OFF) Dec. Equiv.

HR

Step Duration-Hours

MN

Step Duration-Minutes

SC

Step Duration-Seconds

JC

Jump Step

1 or Ch-1 Actual

w2

Wait for Ch-2 Actual

WE

Wait for Event

WH

Wait for Real Hour

WM

Wait for Real Minute

WS

Wait for Real Second

Chart 4 - General Parameter Chart, Chapter 4

Range

Low

High

Units

1

51

Steps

0

3

Type

Ll

U1

°F/°C

L2

u2

0

15

N

0

15

binarv total ON

0

7

binarv total ON

0

7

binarv total ON

0

24

hours

0

59

minutes

0

59

seconds

1 51

Step#

JC Jump Counts 0 255 counts

11

U1

L2 U2

%RH/°F/°C

0

1 -

0

23

hours

0

59

minutes

0

59

,

seconds

WATLOW Series 1500 User's Manual