beautypg.com

Watlow DIN-A-MITE Style C User Manual

Page 4

background image

DIN-A-MITE C Ordering Information

To order, complete the code number on the right with the information below:

Style C solid-state power controller

Phase
1

= single-phase, 1 controlled leg

2

= 3-phase, 2 controlled legs

3

= 3-phase, 3 controlled legs (use with four-wire wye)

8

= 2 independent zones (input control C, K)

9

= 3 independent zones (input control C, K)

Cooling and Current Rating Per Leg
0

= Natural convection standard DIN rail or panel heatsink

1

= Fan-cooled 120V

Å

(ac) standard DIN rail or panel heatsink

2

= Fan-cooled 240V

Å

(ac) standard DIN rail or panel heatsink

3

= Fan-cooled 24V

Î

(dc) fan standard DIN rail or panel heatsink

T = Natural convection through-wall or cabinet heatsink (UL 50)

Line and Load Voltage
02 = 24 to 48V

Å

(ac) (Input Control Signal C, F, or K only)

12 = 100 to 120V

Å

(ac) (Input Control Signal L, P or S only)

20 = 200 to 208V

Å

(ac) (Input Control Signal L, P or S only)

24 = 120 to 240V

Å

(ac) (Input Control Signal C, F or K only);

230 to 240V

Å

(ac) (Input Control Signal L, P or S only)

27 = 277V

Å

(ac) (Input Control Signal L, P or S only)

40 = 400V

Å

(ac) (Input Control Signal L, P or S only)

48 = 480V

Å

(ac) (Input Control Signal L, P or S only)

60 = 277 to 600V

Å

(ac) (Input Control Signal C, F or K only);

600V

Å

(ac) (Input Control Signal L, P or S only)

Input Control Signal
C0 = 4.5 to 32V

Î

(dc) contactor

K1 = 22 to 26V

Å

contactor

K2 = 100 to 120V

Å

contactor

K3 = 200 to 240V

Å

contactor

F0 = Proportional 4 to 20 mA (loop powered)
L(0 to 5) = Phase angle with current limiting (DC1 only, Alarm 0 only,

includes one current transformer - Single phase only)

P(0 to 5) = Phase angle (DC1 only, Alarm 0 only - Single phase only)
S(0 to 5) = Single-cycle variable time base
(Select one of the following input options for L, P, S, (0 to 5))

0 = 4 to 20mA
1 = 12 to 20mA (for Input Control Signal option S only)
2 = 0 to 20mA
3 = 0 to 5V

Î

(dc) proportional

4 = 1 to 5V

Î

(dc) proportional

5 = 0 to 10V

Î

(dc) proportional

Alarm
0

= No alarm

S = Shorted-SCR alarm (not available on Phase options 8 & 9 or Control options L & P)
H = Open-heater and shorted-SCR alarm (for Input Control Signal option S only)

User Manual Language
0

= English

1

= German

2

= Spanish

3

= French

Custom Part Numbers
00 = Standard part
1X = 1-second soft start (control option P, L)
XX = Any letter or number, custom options, labeling, etc.

4

WATLOW DIN-A-MITE Style C User's Manual

__ __ __ __ - __ __ __ __ - __ __ __ __

D C

Current Rating Table

Model

Current

(first 4 digits

at 50°C

of part number) (122°F)

DC10

55 A

DC1T

62 A

DC11, DC12, DC13

75 A

DC20, DC80

40 A

DC2T, DC8T

46 A

DC21, DC22, DC23

65 A

DC81, DC82, DC83
DC30, DC90

30 A

DC3T, DC9T

35 A

DC31, DC32, DC33

55 A

DC91, DC92, DC93

Note:

• Recommended fusing

options to meet 200KA
SCCR, type 1 and 2
approved. All other
fuse and SCR com-
binations are de-
faulted to 5KA SCCR
per UL508A and NEC
guidelines.

Not CE compliant
for conducted or
radiated emissions

Semiconductor Fuses for Applications Through 600V

Å

(ac):

Semiconductor

Watlow Fuse

Bussman Fuse

Watlow Holder

Ferraz Holder

Fuse Rating

P/N

P/N

P/N

P/N

30A

17-8030

FWP30A14F

17-5114

USM141i

40A

17-8040

FWP40A14F

17-5114

USM141i

50A

17-8050

FWP50A14F

17-5114

USM141i

63A

17-8063

FWP63A22F

17-5122

US221i

80A

17-8080

FWP80A22F

17-5122

US221i

100A

17-8100

FWP100A22F

17-5122