2.3 REPORTING PARAMETERS
The computer can request any of the following for any loop:
Operating parameters:
all of the above
Analog inputs:
sensor input
2.4 COMMUNICATIONS
Types
RS-232, RS-422, or 20ma current loop
Baud rate
jumper selectable, 300 to 9600
Error check
full echo of all settings
Isolation
optical for 20ma, optional for RS-232
Data format
standard ASCII
Display
LED indicates communication active
2.5 CONTROL AND ALARM OUTPUTS
Select up to eight:
Time
proportioning:
voltage output: pulsed 6VDC at 6ma (or
On/Off)maximum -- for solid state or other relays
Analog:
voltage or current: selectable (4 to 20ma, 2 to 10v
etc.)
Display:
LED indicates control output is active
2.6 DIGITAL INPUT OR OUTPUT
2 DigitalOutputs:
opencollector;
true= < 0.5v @ 4ma
false = 5v @ 400ohms
1 Digital Input:
true = < 0.5v; false = > 3.5v
2.7 GENERAL
Power input:
120VAC, 60Hz
Operating ambient:
0 to 50 C
Humidity:
10% to 90%, non-condensing
Enclosures:
NEMA 4, 12, 13 and others optional
Physical:
11.2" wide, 13.25" high, 4" deep
Mounting:
4 bolts; 10.25" wide, 12.25" high
Weight:
approximately 5 pounds