Standard Input Types:

Code Input
J

J thermocouple -50 to 1400 F

K

K thermocouple -110 to 2500 F

T

T thermocouple -120 to 750 F

U

0 to 100%, 0 to 60mv

See hardware sections for scaling milliamp and voltage inputs when using the U
range.

Setpoints for millivolt inputs are in percent of full scale to the nearest 0.1% i.e.,
values from 0000 to 1000.

Setpoints for thermocouple inputs are in degrees F to the nearest degree.

Example: [NOTE: CR is carriage return, LF is line feed]

Command: C3J1200CR

sets loop 3 as J thermocouple with 1200F
setpoint

Response: C3J1200CRLF

To Query for the input type and setpoint:

Command: C(n)QCR

Example:

Command: C3QCR

Response: C3J1200CRLF

7.3 CONTROL CONSTANTS

To set the proportional (gain) value:

K(n)P(abc)CR

K is the constant indicator
n is the loop number 1 to 8
P indicates the proportional constant
abc is the value from 0 to 499

Example:

Command: K5P200CR

sets the proportional gain loop 5 to 200

Response: K5P200CRLF

To query the proportional value:

K(n)PQCR

Example: