7 alarm expander and digital i/o – Watlow 8PID Controller User Manual
Page 27

22
1. As a TTL signal by connecting to "AL" pin and "GND".
ON < 0.5V at 4ma sink
OFF = 5V at 400ohm source resistance
2. To drive A 3-32V type solid state relay. TRUE LOGIC
Connect "AL" pin to - side of control input.
Connect +5V (pin "SP7" for S.N.P2000 and above) to + side of control
input.
When output is on, relay turns on.
When output is off, relay turns off.
3. To drive a 3-32V type solid sate relay. INVERTED LOGIC
Connect "AL" pin to + side of relay.
Connect "GND" pin to - side of relay.
When output is on, relay turns off.
When output is off, relay turns on.
5.7 ALARM EXPANDER AND DIGITAL I/O
The optional alarm expander provides EEROM [memory] storage of control parameters
and is highly recommended in critical situations. The Alarm expander also provides for
22 digital input and output lines. Please see the separate manual for this device.
- 12LS Controller (111 pages)
- 8LS Controller (140 pages)
- Addendum to EZwarePlus (50 pages)
- ANASCAN (62 pages)
- ANASOFT (95 pages)
- ANAWIN 2 (154 pages)
- ANAWIN 3 (23 pages)
- Calibrating Watlow Series 988 Family Process Controls (19 pages)
- CAS (98 pages)
- CAS200 (124 pages)
- CLS (180 pages)
- CLS200 (251 pages)
- CLS200, MLS300 and CAS200 (92 pages)
- Control Console (12 pages)
- CPC400 (230 pages)
- DIN-A-MITE Style A (9 pages)
- DIN-A-MITE Style B (14 pages)
- DIN-A-MITE Style C (22 pages)
- DIN-A-MITE Style D (9 pages)
- DIN-Mount Adapter Instruction Sheet, Rev A (1 page)
- Dual DAC (4 pages)
- EM Gateway (28 pages)
- E-Safe Hybrid Relay Rev B (4 pages)
- E-SAFE II Hybrid Power Switch (4 pages)
- EZwarePlus Programming (264 pages)
- EZ-ZONE PM (111 pages)
- EZ-ZONE PM PID (125 pages)
- EZ-ZONE PM Express Limit (34 pages)
- EZ-ZONE PM Express (35 pages)
- EZ-ZONE PM Integrated Controller (181 pages)
- EZ-ZONE RM Limit Module Rev C (127 pages)
- EZ-ZONE RMA Modul (79 pages)
- EZ-ZONE RMC (236 pages)
- EZ-ZONE RME (124 pages)
- EZ-ZONE RMH (161 pages)
- EZ-ZONE RUI/Gateway (62 pages)
- EZ-ZONE RM-Scanner-Modul (140 pages)
- EZ-ZONE ST (97 pages)
- F4 External Event Board - Rev.B (2 pages)
- HG Series Mercury Displacement Relay (6 pages)
- LogicPro (296 pages)
- Mercury Relay or MDR Retrofit (13 pages)
- MICRODIN (24 pages)
- MICRODIN (106 pages)