Environmental characteristics – Proface PS4800 - 19 Panel PC" User Manual
Page 38
![background image](/manuals/358957/38/background.png)
Characteristics
38
Environmental Characteristics
Characteristics
NOTE: IEC 61131-2 and IP65 are not part of UL certification for hazardous locations.
Characteristics
Value
Standards
Degree of Protection
IP65
EN/IEC 61131-2
Pollution Degree
For use in Pollution Degree 2 environment
EN/IEC 61131-2
Surrounding Air Temperature
during Operation
0...50
°C (32...122 °F)
EN/IEC 61131-2, UL 508
Storage Temperature
– 20...60
°C (– 4...140 °F)
IEC 60068-2-2 tests Bb and Ab,
IEC 60068-2-14 tests Na and
EN/IEC 61131-2
Operating Altitude
2,000 m (6,560 ft) max
EN/IEC 61131-2
Vibration
IACS E10 and EN/IEC 60068-2-
6 Fc
Operation (continuous)
2...9 Hz: 1.5 mm
9...200 Hz: 4.9 m/s
2
5...8.4 Hz: 1.75 mm
8.4...150 Hz: 4.9 m/s
2
Operation (occasional)
2...9 Hz: 3 mm
9...200 Hz: 9.8 m/s
2
5...8.4 Hz: 3.5 mm
8.4...150 Hz: 9.8 m/s
2
Marine Certification
(continuous)
3...13.2 Hz: 1 mm (0.04 in.)
13.2...100 Hz: 6.86 m/s
2
Shock Resistance
(in operation)
147 m/s
2
for a duration of 11 ms
IEC 60068-2-27 Ea test
Surrounding Air Humidity
during Operation
10...85 % RH (Wet bulb temperature: 29
°C
(84.2
°F) max. - no condensation)
EN/IEC 60068-2-78 Cab
Storage Humidity
10...85 % RH (Wet bulb temperature: 29
°C
(84.2
°F) max. - no condensation)
EN/IEC 60068-2-30 Db
Electromagnetic Compatibility
(EMC)
Immunity to High Frequency Interference
EN/IEC 61131-2, IEC 61000-4-x
Electromagnetic Emissions Class A
EN 55022, EN 55011