Hazardous location installations - for atex, Danger – Proface PS4800 - 19 Panel PC" User Manual
Page 25
PS-4700 Series (Atom Z510 Pre-installed Model) User Manual
25
Hazardous Location Installations - For ATEX
The assembled units with an enclosure should be marked:
II 3GD
Ex nA IIA Gc
Ex tc IIIA T92
°C Dc
Tamb: 0
°C to +50°C
DANGER
POTENTIAL FOR EXPLOSION
z
Confirm that the location is free from explosively hazardous gases or dust
before connecting or disconnecting equipment, replacing or wiring modules.
z
The ambient temperature in protective enclosure must not exceed 50
°C (refer
to marking).
z
Mounted in to the category 3D enclosures according to the directive 94/9/EC for
atmosphere with dust.
z
Modules must be mounted into protective enclosure that provides at least the
following degree of protection:
z
IP54 for atmosphere with gas
z
IP6x for atmosphere with dust
z
Do not open the protective enclosure while the system is powered up.
z
Confirm that the power supply has been turned OFF before disconnecting,
replacing or wiring modules.
z
Ensure that the metal parts of component are properly connected to ground.
z
Use only screw fasteners suitable for installations in explosive atmospheres.
z
Do not use damaged equipment.
Failure to follow these instructions will result in death or serious injury.