HMI5000HD Installation Guide
1010-1019 Rev 01 www.maplesystems.com
Environmental Considerations
The HMI5000HD is designed to be mounted inside an enclosure rated
for the installation.
The HMI5000HD operates in temperatures from -20° to 55°C (-4° to
131°F). It is intended for indoor installations and may not be suitable for
use in certain outdoor applications. Avoid installing the HMI5000HDin
environments with severe mechanical vibration or shocks. Do not install
the HMI in enclosures with rapid temperature variations or high
humidity. Either case will cause condensation of water inside the device
and eventual damage to the HMI.
Safety Precautions
Please observe the following precautions when installing the HMI.
Failure to comply with these restrictions could result in loss of life,
serious personal injury, or equipment damage.
Warning: Do not operate the HMI in areas subject to explosion due to
flammable gases, vapors, or dusts.
Warning: Do not connect the HMI to an AC power source. You will
cause permanent damage to the HMI.
Warning: Do not attempt to use a DC power supply that does not meet
HMI power requirements. You may cause malfunction or permanent
damage to the HMI.
Warning: Do not power the HMI with a DC power supply used for
inductive loads or for input circuitry to the programmable
logic
controller. Severe voltage spikes caused by these devices may
damage
the HMI.
Control Panel Design Guidelines
Pay careful attention to the placement of system components and
associated cable routing. These items can significantly enhance the
performance and integrity of your control application.