Vanguard WRM-40 User Manual
Page 34

WRM-10P AND WRM-40 USER’S MANUAL
REV 3
30
e. The following screen will be displayed:
If the tap information is correct, press the
[1]
key (YES) and continue to step f.
If the tap information is incorrect, press the
[2]
key (NO) and return to step d.
f. The following screen will be displayed:
1. YES
Press the
[1]
key (YES) if you wish to convert readings to standard temperature.
The following screen will be displayed:
Press the
[1]
key (COPPER, Tk=234.5) to select copper as the winding material.
Continue to step g.
Press the
[2]
key (ALUMINUM, Tk=225) to select aluminum as the winding
material. Continue to step g.
Press the
[3]
key (MANUALLY ENTER Tk) to manually enter the Tk value. The
following screen will be displayed:
You can increase the Tk value by 0.5
°C increments by pressing the
[PAPER ∧
Contrast]
key.
You can decrease the Tk value by 0.5
°C increments by pressing the
[PAPER ∨
Contrast]
key.
Press the
[ENTER]
key to confirm the temperature setting. Continue to step g.
2. NO
Press the
[2]
key (NO) if you do NOT wish to convert readings to standard
temperature. Continue to step g.
Tk:
230.0
°C
↑↓ to adjust Tk
“ENTER” to accept
WINDING MATERIAL:
4. COPPER, Tk=234.5
5. ALUMINUM, Tk=225
6. MANUALLY ENTER Tk
CONVERT READINGS
TO STANDARD TEMP?
1. YES
2. NO
3 LOWER,N,3 RAISE
IS THIS CORRECT?
1. YES
2. NO