LTCA-10/LTCA-40 USER’S MANUAL

19

5.4 General

Procedures

a. Ground the LTCA-10/40 to substation ground (Item 6 in Figure 1.0, Item 5 in figure 2.0).

WARNING

Always connect the LTCA-10/40 to the substation ground before connecting
test leads to any transformer bushing. Failure to follow this procedure may
damage the LTCA-10/40.

b. Plug the LTCA-10/40 power cable into a power outlet.

c. Insert current-cable plugs and voltage-sensing cable plugs into their respective control

panel jacks.

d. Attach test-cable clamps to the transformer terminals for the winding that is to be

measured.

e. Turn on the LTCA-10/40 power by pressing

[I]

on the rocker switch.

f. Once the power is turned on, the unit will perform self-calibration and display a few start-

up messages. Once the short start-up sequence is completed, the “START-UP” menu will
be displayed (date and time will obviously be different):

1. TEST XFMR

03/04/09

2. SETUP 09:28:03

3. USER DIAG