8. Click on the “OK” button. The following window will be displayed:
9. Type the delay time (in milli-seconds) between the first Open command and the Close
command. Click on the “OK” button. The following window will be displayed:
10. Type the delay time (in milli-seconds) between the Close command and the second
Open command. The following window will be displayed:
11. A 5-second timer will count down, and then the test will be initiated. A sequence of
status messages will be displayed, and when the test is complete, the tabulated results
will be displayed in the VCBA software main window. The test record will also be saved
to a file named TEMP001.DAT in the default test record directory.
NOTE
You can change the default test record directory. Please see section 3.4 for
further information.