Installation (for qualified installers only)

© Travis Industries

4040830

100-01143

Facing Requirements

NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing. If it

does, it is considered a mantel and must meet the mantel requirements listed in this manual.

Face Dimensions

Face

Height

Width

Bottom of Face

Installation Notes

Arched Faces

35-1/2”

21-1/8”

Flush w base of fireplace

Arched top is 25-3/4” radius

Bungalow, T. of L.

35-3/

8”

21-1/8”

Flush w base of fireplace

Vict. Lace

35-1/2”

21-1/8”

Flush w base of fireplace

Looking Glass

36-3/4”

23-1/2”

1-1/4” BELOW base of fireplace

Cast face is approx. 2” thick

Wilmington

36-3/4”

22-1/8”

1-1/4” BELOW base of fireplace

Facing Under 1” Thick

The facing (combustible

or non-combustible)

must maintain a 1/2”

clearance to the sides

and top of the fireplace.

Any material that protrudes

more than 3/4” in front of the

facing is considered a mantel

and must meet the mantel

requirements in this manual.

4-3/4”

30-1/4”

(approx.)

3-3/8”

NOTE: The facing tucks

behind the flanges.

NOTE The facing tucks under the notch at the front

of the fireplace (3/8” above the base of the fireplace).

a

b

c

Recommended Order of Installation We

recommend installing the facing (drywall, tile)

under the notch at the front of the fireplace

(“a”) - then install the sides and top (“b” and

“c”)

Facing Over 1” Thick

Facing that protrudes in front of the face above the face (or within 1/2” of each side) must be
made of non-combustible materials.

NOTE A 3/8" gap above the face is required for face installation and removal.