Installation (for qualified installers only), Vent configurations with horizontal terminations – Avalon Stoves 21 DV Fireplace User Manual

Page 19

background image

Installation (for qualified installers only)

19

© Travis Industries

4040830

100-01143

Vent Configurations with Horizontal Terminations

Use a single 90°
elbow (NOTE:
an additional
45° elbow may
be used on the
horizontal run).

If using 6-5/8"
diameter vent,
a minimum 12"
vertical rise is
required.

The termination
must fall within
the shaded
area shown in
the chart. Use
the indicated
restrictor
position.

5 feet

10 feet

0 feet

0 feet

5 feet

5 feet

0 feet

0 feet

10 feet

5 feet

10 feet

14'

(max)

10 feet

Restrictor

Position # 1

14 feet

(max)

14 feet

(max)

14 feet
(max)

NOTE:

If using 6-5/8" diameter vent, a minimum 12" vertical rise is required.

NOTE:

Horizontal sections require a 1/4" rise every 12" of travel.

NOTE:

Restrictor positions are based upon lab tests. The ideal restrictor position