Vanguard ATO-600 User Manual
Page 23

ATO-400 / ATO-600 Operating Procedures
23
Table 5.0 Run Test Procedure (Measure an Unknown Resistance Continued)
STEP
ACTION
ATO DISPLAY
5-10
“RUN ANOTHER TEST?” displays.
5-11
If another test is required, press key #1
(YES). The SELECT TEST CURRENT
menu will appear.Go to step 5-12.
If another test is not required, then press
key #2 (NO) and go to step 5-15.
5-12
Return to step 5-2 to setup for another test
Repeat the sequence from step 5-2 to step
5-10.
Step 5-2 thru 5-10 displays repeat.
5-13
“SAVE THIS RECORD?” displays when
another test was not selected in step 5-12.
The test record contains all the readings
taken in this test.
5-14
To save this record, press key #1 (YES). If
the test record is not to be saved, press key
#2 (NO) and go to step 5-16.
NOTE
A test record is saved in Flash
EEPROM. A record number
will be automatically assigned
to the record by the ATO.
(The Test record was assigned
#2 in this example).
5-15
When the record is saved the RECORD
NUMBER “x” shows on display. Press
ENTER to return to the START MENU.
5-16
Pressing key #2 (NO) on SAVE THIS
TEST RECORD (see step 5-14) causes the
ARE YOU SURE? prompt (shown at
right).
ARE YOU SURE?
DATA WILL BE LOST!
1. DO NOT SAVE RECORD
2. SAVE RECORD
1. RUN TEST 04/11/05
2. SETUP 12:24:01
3. DIAGNOSTIC
RECORD NUMBER 2
HAS BEEN SAVED!
SAVE THIS TEST RECORD?
1. YES
2. NO
SELECT TEST CURRENT:
1. 10A 2. 25A 3. 50A
4. 100A 5. 200A 6. 300A
7. 400A 8. CUSTOM
RUN ANOTHER TEST?
1. YES
2. NO