Thermal specifications, General specifications, Output specifications – TREND RN User Manual
Page 9: Input specifications

2
Specifications are subject to change without notice (30.09.2005)
Thermal Specifications
RN.F..30
RN.F..50
Operational temperature
-20° to +70°C (-4° to +158°F)
-20° to +70°C (-4° to +158°F)
Storage temperature
-20° to +100°C (-4° to +212°F)
-20° to +100°C (-4° to +212°F)
Junction temperature
< 125°C (257°F)
< 125°C (257°F)
R
th
junction to ambient (AC load)
2.8 K/W
1.7 K/W
General Specifications
RN.F12...
RN.F23...
RN.F48...
Operational voltage range
85 to 140 VAC
85 to 265 VAC
190 to 530 VAC
Non-rep. peak voltage
800 V
p
800 V
p
1000 V
p
Varistor voltage
275 VAC
275 VAC
510 VAC
Zero voltage turn-on
< 10 V
< 10 V
< 20 V
Operational frequency range
45 to 65 Hz
45 to 65 Hz
45 to 65 Hz
Power factor at rated voltage
≥
0.9
≥
0.9
≥
0.9
Average output power
0 to 100%
0 to 100%
0 to 100%
Output power resolution
1/64 of 100%
1/64 of 100%
1/64 of 100%
Approvals
UL, cUL, CSA
UL, cUL, CSA
UL, cUL, CSA
CE-marking
Yes
Yes
Yes
Norms fulfilled
EN 60947-1 Low-voltage switchgear and control gear. Part 1- General Rules.
EN 61000-6-1 Generic Immunity Standard. Residential, Commercial & Light Industry Environment
EN 61000-6-2 Generic Immunity Standard. Industrial Environment
Output Specifications
RN.F..30
RN.F..50
Rated operational current
RN1F..
AC51
@Ta=30°C
30 A
50 A
“
@Ta=40°C
30 A
50 A
“
@Ta=50°C
23 A
38 A
“
@Ta=60°C
20 A
30 A
RN2F..
AC51
@Ta=30°C
30 A total sum (2 x 15A)
50 A total sum (2 x 25A)
“
@Ta=40°C
30 A total sum (2 x 15A)
50 A total sum (2 x 25A)
“
@Ta=50°C
23 A total sum (2 x 11.5A)
38 A total sum (2 x 19A)
“
@Ta=60°C
20 A total sum (2 x 10A)
30 A total sum (2 x 15A)
Zero crossing detection
Yes
Yes
Min. operational current (per pole)
500 mA
500 mA
Rep. overload current t=1 s
(Tj init.=25°C)
55 A (rms)
125 A (rms)
Non-rep. surge current t=10 ms
(Tj init.=25°C)
< 300 A
p
< 580 A
p
Off-state leakage current,
@ rated voltage and frequency
(Tj.=125°C, max.)
< 6 mA
< 6 mA
I
2
t for fusing t=1 to 10 ms
450 A
2
s
1680 A
2
s
Critical dV/dt off-state
500 V/µs
500 V/µs
RN 1F
Input Specifications
RN.F..I..
Current controlled input
Control current range
4 - 20 mA
Allowable input current
50 mA
Reverse polarity protected
Yes
Voltage drop
10 VDC @ 20 mA
RN.F..V..
Voltage controlled input
Supply voltage range
21 - 27 VAC, 12 - 32 VDC
Supply current
30 mA @ 24 VAC/32 VDC
Control voltage range
0 - 10 V
Control input current
0.1 mA @ 10 VDC