Insulation, Dimensions, Housing specifications – TREND RN User Manual
Page 10: Environment specifications, Wiring diagrams, Or 2 x 2.5 mm, Or 2 x 6 mm, Humidity max. 95%, no condensation rn 1f, Single-pole relay double-pole relay, Rn rn
Specifications are subject to change without notice (30.09.2005)
3
Insulation
Rated impulse withstand voltage
Input to output
4000 V
imp
Rated impulse withstand voltage
Output to heatsink
4000 V
imp
Dimensions
Dimensions
(H x W x D)
RN..30
120 x 45 x 110 mm
RN..50
120 x 90 x 110 mm
Housing Specifications
Mounting
DIN-rail 35 mm
Weight with RHN1
470 g
Weight with RHN2
780 g
Housing material
Noryl SEI, GFN1, Black
LED window material
PC Lexan 141R
Base plate
Aluminium, nickel plated
Potting compound
Polyurethane, Casco Nobel
Terminals
Screw with captive wire clamp
Control terminals nominal
4 mm
2
or 2 x 2.5 mm
2
AWG 12 or 2 x AWG 14
Min.
0.5 mm
2
, AWG 20
Mounting torque max.
0.6 Nm
Power terminals nominal
10 mm
2
or 2 x 6 mm
2
AWG 6 or 2 x AWG 10
Min.
1 mm
2
, AWG 16
Mounting torque max.
2.0 Nm
Heatsink compound used
Electrolube HTS
Environment Specifications
Humidity max.
95%, no condensation
RN 1F
Dimensions
4
120
45
33,7
103
71,6
37
30
20
70
60
4
120
93
72
45
89
103
71,6
37
20
70
30
60
Note: all dimensions in mm
Wiring Diagrams
L
1
A
1
A
2
T
1
4 - 20 mA
+
Current Control
_
L
1
A
1
A
2
T
1
A
3
A
4
0 - 10 VDC
+
Voltage Control
_
Control
Supply
L
1
A
1
A
2
T
1
4 - 20 mA
+
Current Control
_
L
1
A
1
A
2
T
1
A
3
A
4
0 - 10 VDC
+
Voltage Control
_
Control
Supply
L
2
L
2
T
2
T
2
Single-pole relay
Double-pole relay
Note: all dimensions in mm
RN..30
RN..50