TB/TI Thermistor Insertion Temperature Sensor Installation Instructions TG200727 Issue 1/E 11/07/07

5

Installation Instructions

TB/TI

Installation

(continued)

Remove Lid

5

Insert Cable

6

either use M20 flexible conduit

or use M16 cable gland

Wire to Controller

7

Replace Lid

8

Sensor

IQ1xx/2xx

COM (0V)

IN

polarity
independent

Analogue input
channel linked for
thermistor (T)

terminate screen at
IQ end only

T

terminal size 0.5 to 2.5 mm

2

(14 to 20 AWG)

TP/1/1/22/HP/200 (Belden 8761) cable recommended

Note that IP67 (NEMA6) rating is only
achieved if the sensor is correctly installed
with cable or conduit connection fully
tightened.

Sensor

IQ3

0 (0V)

N (in)

+ (24 V)