T/fs data sheet, Specifications, Trend control systems limited – TREND T_FS User Manual
Page 4: Trend control systems usa
T/FS
Data Sheet
4
T/FS Frost Protection Thermostat Data Sheet 91-2777 Issue 2 03/04/08
Trend Control Systems Limited
P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com
Trend Control Systems USA
6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com
Please send any comments about this or any other Trend technical publication to [email protected]
© 2008 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 3, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions or changes.
SPECIFICATIONS
Product description
:T/FS frost protection thermostat
Measuring range
:-10 to +12 °C (14 °F to 54 °F)
Sensing element
:6 metre (6.5 yds) gas filled copper
capillary
Ambient limits
:-20 to +80 °C (-4 °F to +176 °F), 0 to 95%
RH non-condensing
Control action
:Single pole, single throw circuit opens
on fall of temperature
Electrical rating
:15 A, 250 Vac
Connections
:Screw terminals for 0.5 to 4 mm
2
(12 to
26 AWG) cable
Environmental
Protection
:IP54 (NEMA 3)
Accuracy :±2°C
Dimensions
Sensing element
:3.2 mm (0.13”) dia. x 6 m (6.5 yds) long
Minimum bending radius
of sensing element
:20 mm (0.79”)
Housing
:130 mm x 130 mm x70 mm (5.12” x 5.12”
x 2.76”) (with mounting bracket)
Fixing centres
:120 mm (4.72”)
Cable entry
:22 mm (0.87”) diameter cut-out fitted
with rubber grommet
Material
Sensing element
:Copper/Tin plated
Housing
:Base polyamide, cover polycarbonate
(V-0)
Fixing clips
:Polyamide (V-0)