Self-Restoring Rate-of-Rise (ROR) Sensor
The rate-of-rise element responds to a rapid rise of
temperature, approximately 15ºF (8.3ºC) per min-
ute. As the temperature rises, the air within the
sealed chamber expands. Should the chamber air
expand faster than it can escape through the cali-
brated vent, the diaphragm is depressed, and the
electrical contact closes the circuit.
NOTE: Only the ROR element of 5600 series com-
bination fixed temperature/ROR models (5601P,
5602, 5621, and 5622) are self-restoring, and may be
tested using a hair dryer or heat gun. When testing
the ROR element, to prevent the activation of the
fixed temperature element, the heat source must not
exceed the fixed temperature rating of the detector.
Mounting Bracket
All 5600 series detectors are equipped with a mount-
ing bracket that includes mounting slots to accom-
modate single-gang, 3
1
⁄
2
˝ octagonal, and 4˝ octagonal
electrical boxes, as well as 4˝ square boxes equipped
with a plaster ring (Figure 1). The mounting bracket
is reversible to accommodate flush-mount and sur-
face–mount installations (Figure 2).
Wiring Installation Guidelines
All wiring must be installed in compliance with the
National Electrical Code, applicable state and local
codes, and any special requirements of the local
Authority Having Jurisdiction. Proper wire gauges
should be used. The conductors used to connect
heat detectors to the alarm control panel and ac-
cessory devices should be color-coded to reduce the
D500-46-00
2
I56-2175-003R
Heat Detector Type
RTI Classification
Fixed 135°F RTI:
SPECIAL
RoR and Fixed 135°F RTI:
ULTRA FAST and SPECIAL (Respectively)
Fixed 194°F RTI:
SPECIAL
RoR and Fixed 194°F RTI:
ULTRA FAST and SPECIAL (Respectively)
FM Classification
RTI ratings are for installations which must comply with FM 3210.
Table 1. 5600 Series Mechanical Heat Detectors
Model
No.
Circuit
Temperature
Rating
Thermal Sensor
UL Maximum Spacing
(10-foot ceiling)
5601P
Single
135ºF (57ºC)
Fixed Temperature/Rate of Rise
50-feet x 50-feet
5602
Single
194ºF (90ºC)
Fixed Temperature/Rate of Rise
50-feet x 50-feet
5603
Single
135ºF (57ºC)
Fixed Temperature
25-feet x 25-feet
5604
Single
194ºF (90ºC)
Fixed Temperature
25-feet x 25-feet
5621
Dual
135ºF (57ºC)
Fixed Temperature/Rate of Rise
50-feet x 50-feet
5622
Dual
194ºF (90ºC)
Fixed Temperature/Rate of Rise
50-feet x 50-feet
5623
Dual
135ºF (57ºC)
Fixed Temperature
25-feet x 25-feet
5624
Dual
194ºF (90ºC)
Fixed Temperature
25-feet x 25-feet
NOTE: Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet.
A= 3
1
⁄
2
˝ Octagonal box
B= 4˝ Octagonal box
C= Single gang box and 4˝
square with plaster ring
D= Directly to Wall/Ceiling
Figure 1. Bracket Mounting Locations:
S0113-00
S0114-00
S0115-00
Surface–mount
Flush–mount
Figure 2. Reversible Mounting Bracket: