System Sensor 5600 Series Heat Detectors User Manual
System Sensor Equipment
Before Installing
This detector must be installed in compliance with
the control panel installation manual and meet the
requirements of NFPA 72, and/or the local authority
having jurisdiction.
Read this manual carefully before using the detec-
tor. This manual should be left with the owner/user
of this equipment.
General Description
The 5600 series mechanical heat detector is in-
tended for use in property protection applications,
or for non-life-safety installations where smoke de-
tection is not practical or appropriate.
WARNING
For life-safety installations, smoke detectors must
be used, in lieu of, or in addition to mechanical heat
detectors.
The 5600 series consists of both single- and dual-
circuit heat detectors featuring fixed temperature
thermal sensors or combination fixed temperature/
rate-of-rise sensors, with temperature ratings of 135ºF
(57ºC) or 194ºF (90ºC).
D500-46-00
1
I56-2175-003R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
5600 Series
Mechanical Heat Detector
Single Circuit: 5601P, 5602, 5603, 5604
Dual Circuit: 5621, 5622, 5623, 5624
Markings on the exterior of the detector indicate the
specific activation method and temperature rating. All
models are identified as either 135ºF/57ºC or 194ºF/
90ºC. Models equipped with combination fixed tem-
perature/rate-of-rise sensors are marked FX/ROR.
Fixed temperature only models are marked FX.
Non-Resettable Fixed Temperature Sensor
The fixed temperature element reacts to heat by re-
sponding to a specific temperature setting (135ºF
or 194ºF). The detection method is based on the
spring action of a metal contact, held to the metal
chamber by a fusible alloy. When the temperature
reaches the alloy’s melting point, the metal contact
will depress the diaphragm, causing the electrical
contact to close the circuit. The circular external
heat collector is released from the detector to visu-
ally indicate that the detector has been activated.
NOTE: 5600 series Fixed Temperature models (5603,
5604, 5623, and 5624) are non-resettable, and can-
not be tested.
Specifications:
Operating Voltage/Contact Ratings (Resistive): 6 – 125 VAC / 3A
6 – 28 VDC / 1A
125 VDC / 0.3A
250 VDC / 0.1A
Maximum Installation Temperature:
Models 5601P, 5603, 5621, and 5623: 100°F (38°C)
Models 5602, 5604, 5622, and 5624: 150°F (65.6°C)
Alarm Temperature:
Models 5601P, 5603, 5621, and 5623: 135°F (57°C)
Models 5602, 5604, 5622, and 5624: 194°F (90°C)
Rate-of-Rise Threshold:
15°F (8.3°C) per minute
(models 5601P, 5602, 5621, and 5622 only)
Operating Humidity Range:
5 to 95% RH non-condensing
Input Terminals:
14 – 22 AWG
Back Box Mounting:
3
1
⁄
2
˝ octagonal
4˝ octagonal
Single gang
4˝ square with a square to round plaster ring
Dimensions with mounting bracket:
Diameter: 4.57 inches (11.6cm)
Height: 1.69 inches (4.3cm)
Weight:
6 oz. (170 grams)
CAUTION
To prevent the activation of the fixed temperature element, the shipping and storage temperature must not
exceed 122°F (50°C).