Model

Volts

Watt/ft

Maximum

Single Run Length

SR123

120V

3 w/ft

325 ft. (99M)

SR125

120V

5 w/ft

270 ft. (82M)

SR128

120V

8 w/ft

210 ft. (64M)

SR1210

120V

10 w/ft

180 ft. (55M)

Volts

Start up

Temp.

Circuit

Breaker*

SR123

3w/ft.

SR125

5w/ft.

SR128

8w/ft.

SR1210

10w/ft.

120 V

50ºF

(10ºC)

15 Amp

325 ft. (99M)

225 ft. (69M)

145 ft. (44M)

115 ft. (35M)

20 Amp

435 ft. (133M)

270 ft. (82M)

195 ft. (59M)

150 ft. (46M)

0ºF

(-18ºC)

15 Amp

230 ft. (70M)

155 ft. (47M)

100 ft. (30M)

85 ft. (26M)

20 Amp

305 ft. (93M)

205 ft. (72M)

130 ft. (40M)

110 ft. (34M)

-20ºF

(-29ºC)

15 Amp

205 ft. (63M)

135 ft. (41M)

90 ft. (27M)

75 ft. (23M)

20 Amp

275 ft. (84M)

180 ft. (55M)

115 ft (35M)

100 ft. (30M)

Table 3: Maximum Single Cable Length

The maximum length of a single cable run is noted in Table 3
and cannot be exceeded. If the application requires a longer
cable run, then multiple cables and additional power circuits
must be used.

Circuit protection depends on the length of cable required
and the start-up temperature since the cable will draw more
power (wattage) when cold. Multiple cables can be run from
a single power circuit up to a maximum combined length as
noted in Table 5. Larger amperage circuits breakers can
handle longer combined cable lengths, but the maximum
length for a single cable run does not change. The NEC
requires the use of ground fault protection breakers for
heating cable.

Table 5: Circuit Protection Per Combined Cable Length for Pipe Freeze Protection

Circuit Breaker Protection and Cable Length Design for Pipe Freeze Protection