King Electric SRK12 end-seal kit User Manual
Srk12 end seal kit, Important: save these instructions
SRK12 End Seal Kit
DESCRIPTION:
SR
self-regulating
heating
cables
are designed
for
a variety of pipe
freeze
protection
as well as roof
and gutter deicing applications. The heat output
(wattage)
increases and decreases based on the
temperature, so the cable adjusts automatically to
varying climate conditions. This unique feature
ensures maximum energy efficiency by increasing
the heat output only when it is needed. No
thermostat is required
.
Item
Qty
Description
A
2
Black heat shrink tube (3/4” dia. x 5” length)
B
2
Woven braid sleeve ( ½” dia. x 4” length)
C
2
Black heat shrink cap ( ½” dia. x 1-1/4” length)
www.king-electric.com
Rev. 8.13.12
Telephone: 206-762-0400 pg1
Installation, Operation and Maintenance Instructions
IMPORTANT: Save These Instructions!
WARNING: ELECTRIC SHOCK HAZARD
Disconnect all power before installing or servicing
the heating cable and accessories. SR heating
cable must be grounded properly in accordance
with the National Electrical Code (NEC). Failure to
comply can result in personal injury or property
damage. Only a qualified licensed electrical
contractor shall install and service of SR heating
cable and accessories, otherwise the warranty is
voided.
Note:·All electrical wiring, including Ground Fault
Circuit Interrupters (GFCI), must be done according
to the NEC and local codes by a qualified installer.
Article 426 of ANSI/NFPA 70 of National Electrical
Code (NEC section 62 of CAN/CSA-C22.1,
Canadian Electrical Code, Part I(CEC) governs the
installation of this heat systems
Score the outer jacket 2” from the end
of the cable.
CAUTION: When removing the outer
jacket, be careful not to damage the braid
or the base cable insulation.
Remove the outer jacket to expose
the braid.
Push the braid back off the end of the
cable.
WARNING: ELECTRIC SHOCK HAZARD
Do not connect the bus wires together.
Keep braid out of heat shrink cap.
1
2
3