King Electric SRK08 GFEP device kit User Manual
Page 15
Rev 11.04.12
www.king-electric.com
15
17
Center the 8” heat shrink tube over the entire splice,
make sure it extends over the end heating cable and
the cord. Start at the middle and work toward each
end.
18
19
20
Use the un-insulated connector with a crimp tool to
connect braid to green ground wire. Wrap the
connector with the black cloth tape. Cover crimped
connector completely.
Shrink the tubing completely.
Completed splice
Cover crimped connector completely.
See also other documents in the category King Electric Accessories for electrical:
- SRK00 pipe mount kit (16 pages)
- SRK02 connection kit (7 pages)
- SRK10 splice/tee kit (8 pages)
- SRK12 end-seal kit (2 pages)
- SRK13 roof clip (2 pages)
- SRK15 downspout hanger (2 pages)
- SST 2 (14 pages)
- SST 3 (28 pages)
- GPT 3 (21 pages)
- LCD-7A (2 pages)
- N.E.M.A.4X TF115 (2 pages)
- DS-824 (4 pages)
- DS-8 (4 pages)
- DS-2B (4 pages)
- CDP-2 (2 pages)
- TH115-AF-GA Electronic Programmable (76 pages)
- TH114-AF-GA Electronic Non-Progrm (2 pages)
- TH115-AF-12VDC Electronic Progrm Master (4 pages)
- FCS13 heating cable repair kit (4 pages)
- FCS11 Instant Alert Monitor (2 pages)
- F802GFCI Electronic Programmable (6 pages)
- FCM Floor Mat (19 pages)
- SRP self-reg, preassembled (6 pages)
- CWP (4 pages)
- SC (20 pages)
- TC (11 pages)
- ES Electronic (3 pages)
- ESP Electronic Programmable (4 pages)
- ECP2P Electronic Programmable (4 pages)
- HE Anticipated (2 pages)
- K601C-25 Heat or Cool (2 pages)
- WR Window Watcher (4 pages)
- K101 (3 pages)
- HWP120 Electronic Programmable (1 page)
- Transformer Silent Relay (3 pages)
- Transformer Silent Relay (1 page)
- Bi-metal Sensor Thermostat (1 page)
- Capilary Tube Thermostat (1 page)