Table 11: maximum single run length – King Electric SRK08 GFEP device kit User Manual
Page 11
![background image](/manuals/350888/11/background.png)
Model
Volts
Output at
32ºF (0ºC)
Maximum
Single Run
Length
SR123
120V
5.0 w/ft
273 ft. (83M)
SR125
120V
8.0 w/ft
216 ft. (66M)
SR128
120V
12.1 w/ft
171 ft. (52M)
SR1210
120V
14.8 w/ft
152 ft. (46M)
Rev 11.04.12
www.king-electric.com
11
Technical Data Table
Maximum operating temp.
150°F (65°C)
Maximum exposure temp.
185°F (85°C)
Minimum installation temp.
0°F (-18°C)
Minimum bending radius
1”, (24 mm)
Dimensions
.496” x .236”
(12.6mm x 6mm)
Service voltage
110-120V,
208V-277V
Cable
Volts
Start up
Temp
15 Amp
(ft.)
20 Amp
(ft.)
30 Amp
(ft.)
40 Amp
(ft.)
SR123
120V
32ºF (0ºC)
273
273
273
273
20ºF (-7ºC)
254
268
273
273
0ºF (-18ºC)
213
255
273
273
-20ºF (-29ºC)
182
248
273
273
SR125
120V
32ºF (0ºC)
188
216
216
216
20ºF (-7ºC)
166
216
216
216
0ºF (-18ºC)
144
193
216
216
-20ºF (-29ºC)
127
173
216
216
SR128
120V
32ºF (0ºC)
126
168
171
171
20ºF (-7ºC)
118
157
171
171
0ºF (-18ºC)
103
136
171
171
-20ºF (-29ºC)
92
123
168
171
SR1210
120V
32ºF (0ºC)
102
143
152
152
20ºF (-7ºC)
97
126
152
152
0ºF (-18ºC)
88
117
152
152
-20ºF (-29ºC)
76
104
152
152
Table 9: Circuit Breaker Protection for Deicing
Table 10: Technical Data Ratings
Table 11: Maximum Single Run Length
Technical Data Notes:
1. The maximum single cable run is the longest length of heating cable before there is a
significant voltage drop which will lower the wattage rating of the cable.
2. The circuit breaker sizes in Table 9 are per the National Electric Code (NEC).
3. The NEC requires ground-fault equipment protection (GFEP) for fixed outdoor deicing
equipment. All electrical connections should be made by a licensed electrician.
Circuit Breaker Protection and Cable Length Design for Deicing