Table 11: maximum single run length – King Electric SRK08 GFEP device kit User Manual

Page 11

background image

Model

Volts

Output at

32ºF (0ºC)

Maximum

Single Run

Length

SR123

120V

5.0 w/ft

273 ft. (83M)

SR125

120V

8.0 w/ft

216 ft. (66M)

SR128

120V

12.1 w/ft

171 ft. (52M)

SR1210

120V

14.8 w/ft

152 ft. (46M)

Rev 11.04.12

www.king-electric.com

11

Technical Data Table

Maximum operating temp.

150°F (65°C)

Maximum exposure temp.

185°F (85°C)

Minimum installation temp.

0°F (-18°C)

Minimum bending radius

1”, (24 mm)

Dimensions

.496” x .236”

(12.6mm x 6mm)

Service voltage

110-120V,

208V-277V

Cable

Volts

Start up

Temp

15 Amp

(ft.)

20 Amp

(ft.)

30 Amp

(ft.)

40 Amp

(ft.)

SR123

120V

32ºF (0ºC)

273

273

273

273

20ºF (-7ºC)

254

268

273

273

0ºF (-18ºC)

213

255

273

273

-20ºF (-29ºC)

182

248

273

273

SR125

120V

32ºF (0ºC)

188

216

216

216

20ºF (-7ºC)

166

216

216

216

0ºF (-18ºC)

144

193

216

216

-20ºF (-29ºC)

127

173

216

216

SR128

120V

32ºF (0ºC)

126

168

171

171

20ºF (-7ºC)

118

157

171

171

0ºF (-18ºC)

103

136

171

171

-20ºF (-29ºC)

92

123

168

171

SR1210

120V

32ºF (0ºC)

102

143

152

152

20ºF (-7ºC)

97

126

152

152

0ºF (-18ºC)

88

117

152

152

-20ºF (-29ºC)

76

104

152

152

Table 9: Circuit Breaker Protection for Deicing

Table 10: Technical Data Ratings

Table 11: Maximum Single Run Length

Technical Data Notes:

1. The maximum single cable run is the longest length of heating cable before there is a

significant voltage drop which will lower the wattage rating of the cable.

2. The circuit breaker sizes in Table 9 are per the National Electric Code (NEC).

3. The NEC requires ground-fault equipment protection (GFEP) for fixed outdoor deicing

equipment. All electrical connections should be made by a licensed electrician.

Circuit Breaker Protection and Cable Length Design for Deicing