TROUBLESHOOTING


If any unusual condition occurs with the unit, refer to troubleshooting charts 1 and
2 in this section. Prior to removal of any equipment, contact Environmental
Technology, Inc., Technical Support at (800) 234-4239

between 8:00 a.m. and

5:00 p.m., Eastern Time,

to begin the troubleshooting process.

LL Fault

on display

PRB Fault

on display

Install

temperature

probe

Is

temperature

probe

installed

Possibly

faulty probe

should be

100K ohm at

70 degree F

Replace

probe

Possible heater

issue. Not

connected properly

or heater failure

Temperature is

at least 4

degrees less

than set point

Low

temperature

limit fault

Re-position

probe

Temperature

probe

fault

Is

temperature

probe installed

in proper

location

Are heaters

getting warm or

hot?

Was the

unit just installed

or was power

off?

Normal operation

wait for heaters

to bring system

to operating

temperature

Yes

No

Yes

Yes

Yes

No

No

No

SST-3

troubleshooting

charts

TROUBLESHOOTING FLOWCHART 1.