KB Electronics KBPW-240D User Manual

Page 10

background image

operation (230 Volt AC line input with 90
Volt DC SCR rated motor or 130 Volt DC
PWM rated motor) set jumper J1 to
“90V” position. However, in step-down
operation the motor may have reduced
brush life - consult motor manufacturer.

Note: Do not connect motor armature
leads to F1 and F2 terminals. Do not
use F1 and F2 terminals for PM motors.

D. Full Voltage Field Connection (Shunt

Wound Motors Only) – Wire the motor
field leads to F1 (+) and F2 (-) terminals
of TB2 as shown in Figure 4 and Table 4.

Note: Do not connect motor armature leads to F1 and F2 terminals.

Warning! Do not use F1 and F2 termi-
nals of TB2 for any purpose other than
to power the field of a shunt wound
motor.

E. Half Voltage Field Connection (Shunt

Wound Motors Only) – Wire the motor
field leads to F1 (+) and L1 (-) terminals
of TB2, as shown in Figure 5 and Table 4.

Note: Do not connect motor armature
leads to F1 and F2 terminals.

Warning! Do not use F1 and F2 termi-
nals of TB2 for any purpose other than
to power the field of a shunt wound
motor.

F. Remote

Main

Speed

Potentiometer

Connection – The control is supplied with a
prewired main speed potentiometer mounted
on the front cover. To operate the control from
a remote potentiometer (5kΩ), remove the
white, orange, and violet potentiometer leads
from P1, P2, and P3 terminals, respectively.
The leads may be taped and left inside the
control. The potentiometer assembly may be
removed if a watertight seal is used to cover
the hole in the front cover. Connect the
remote main speed potentiometer wires to
terminals P1 (low side), P2 (wiper), and P3
(high side) as shown in Figure 6.

7

+

M

+

-

MOTOR

AC LINE

-

FIELD

GROUND

(EARTH)

L2

L1

A1

A2

TB2

TB1

F1

F2

FIGURE 4 – FULL VOLTAGE FIELD

AC LINE

-

-

+

+

MOTOR

M

(EARTH)

FIELD

GROUND

L2

L1

A2

A1

TB2

F1

F2

TB1

FIGURE 5 – HALF VOLTAGE FIELD

Field Connections

F1 & L1

AC Line Voltage

(Volts AC)

Armature Voltage

(Volts DC)

Field Voltage

(Volts DC)

90 – 130

115

115

230

180 – 260

230

230

90 – 130

180 – 260

90 – 130

100

50

200

100

100

F1 & F2

F1 & L1

F1 & F2

F1 & L1

TABLE 4 – FIELD CONNECTION (Shunt Wound Motors Only)

(FRONT VIEW)

Wiper

Low Side

High Side

POTENTIOMETER

MAIN SPEED

TACH

P3

P2

P1

RELAY

TB4

K1

K2

T+

TB3
T-

FIGURE 6 – REMOTE POTENTIOMETER