M. boiler piping details – HTP 850 LPHL User Manual
Page 20
![background image](/manuals/350200/20/background.png)
20
LP- 205 REV. 3.28.14
M. BOILER PIPING DETAILS
Figure 8
– Single Boiler Space Heating – Indirect Priority
FIGURE NOTES:
1. This drawing is meant to demonstrate system piping concept only.
2. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119
o
F.
3. Install a minimum of 12 diameters of straight pipe upstream of all circulators.
4. Install a minimum of 6 diameters of straight pipe up and downstream of all closely spaced tees.
5. Piping shown is Primary/Secondary.
6. The minimum pipe size for conn
ecting an HTP indirect fired water heater is 1”.
7. The minimum pipe size for connecting a Mod Con boiler is 1 ½” for the 300 and 2” for the 500 and 850.
8
. System flow (Secondary Loop) must be greater than the boiler’s Primary Loop flow.
9. Installations must comply with all local codes.
10. In Massachusetts, a vacuum relief valve must be installed on the cold water line per 248 CMR.