H. HIGH VELOCITY CIRCULATOR PUMP

The heat exchanger has a minimum total water volume that must be taken into account when sizing the circulator. These minimum
water volumes are listed in Table 5 below.

MINIMUM HEATER FLOW RATES

MODEL

MINIMUM FLOW (GPM)

EL-80 VWH

5.3

EL-110 VWH

7.3

EL-150 VWH

10

EL-220 VWH

14.6

El-299/301 VWH

20

El-399 VWH

26

Table 5

– Minimum Heat Exchanger Water Volumes

Every VWH system requires special attention to pump size in order to overcome pressure drop through the heater and its related
piping. All circulators installed on the VWH system must be designed for a potable water system.

ELITE VWH CIRCULATORS

MODEL

CIRCULATOR

PART #

FLANGE SIZE

FLANGE PART #

EL-80 VWH

009-SF5

7450P-239

1” NPT

7450P-242

EL-110 VWH

0011-SF4

7450P-240

1” NPT

7450P-242

EL-150 VWH

0013-SF3

7450P-241

1” NPT

7450P-242

EL-220 VWH

0013-SF3

7450P-241

1” NPT

7450P-242

EL-299/301 VWH

2400-20S

7250P-605

1 ¼” NPT

7250P-603

EL-399 VWH

2400-50S

7250P-606

1 ½” NPT

7250P-604

Table 6

ELITE PUMP KITS

Elite 80 VWH

– Part # 7450P-246

Elite 110 VWH

– Part # 7450P-247

Elite 150 and Elite 220 VWH

– Part # 7450P-248

Elite 299/301 VWH

– Part # 7450P-249

Elite 399 VWH

– Part # 7450P-250

The chart below represents the various system design temperature rise through the heater along with their respective flows and friction
loss, which will aid in circulator selection.

HEAT EXCHANGER PRESSURE DROP CHART

Model

Flow Rate Δ P’

Flow
Rate

6

GPM

7 GPM

8

GPM

9

GPM

10

GPM

11 GPM

12

GPM

13

GPM

14

GPM

15

GPM

16

GPM

17

GPM

18

GPM

19

GPM

20

GPM

21

GPM

22

GPM

EL-80

10’

14’

17’

21’

26’

*

*

*

*

*

*

*

*

*

*

*

*

EL-110

*

*

15’

17’

22’

25’

33’

*

*

*

*

*

*

*

*

*

*

EL-150

*

*

*

*

12’

15’

17’

19’

22’

27’

*

*

*

*

*

*

*

EL-220

*

*

*

*

*

*

*

*

*

8’

10’

11.5’

13’

15’

16.5’

17’

19’

EL-299

EL-301

*

*

*

*

*

*

*

*

*

*

*

*

*

*

13’

14’

15’

EL-399

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

Flow
Rate

23

GPM

24

GPM

25

GPM

26

GPM

27

GPM

28

GPM

29

GPM

30

GPM

31

GPM

32

GPM

33

GPM

34

GPM

35

GPM

36

GPM

37

GPM

38

GPM

39

GPM

EL-80

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-110

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-150

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-220

21’

23’

24’

*

*

*

*

*

*

*

*

*

*

*

*

*

*

EL-299

EL-301

16.5’

18’

20’

22’

24’

26’

29’

33’

36’

*

*

*

*

*

*

*

*

EL-399

*

*

*

12.9’

13.6’

14’

15.7’

17’

18’

19.4’

21’

22.5’

26’

28’

31’

34’

39’

Table 7 -

*Do not operate heater at these flow settings as it will damage the heat exchanger or related components cause by excessive flow

rates or minimum flow rates.