Maintenance – Robinair 34288 Recovery, Recycling, Recharging Unit User Manual

Page 16

background image

14

5 . .The .display .reads .PLEASE .REPLACE .FILTER . .

Open .the .rear .door .of .the .unit .and .unscrew .the .old .

filter . .See .Figure .8 . .

6 . .Look .at .the .new .filter—verify .both .o-rings .are .

lubricated .and .correctly .located .in .the .grooves . .See .

Figure .9 . .Thread .the .new .filter .into .place . .Press .

START / YES .

Note: If the display shows SERIAL .NUMBER .ERROR,

the serial number is invalid or the filter-drier has

already been used in this unit.
7 . .Close .the .door . .Press .STOP / NO .to .exit . .The .filter-

drier .replacement .is .now .complete .

Replace the Filter-Drier contd.

Maintenance

Filter-Drier

Rear View

(without shroud)

Adjust Tank Fill Level

When .connected .to .a .refrigerant .source, .the .unit .

maintains .a .default .value .of .15 .lbs . .of .refrigerant .in .the .

internal .storage .vessel . .This .value .may .be .adjusted .up .

or .down .to .suit .the .application . .
1 . .Press .MENU .
2 . .Use .the .arrow .keys .to .scroll .through .the .menu .to .

ADJUST .TANK .FILL .LVL, .and .press .START /

YES . .The .unit .displays

LEVEL: .15 .00 .LBS .

ENTER .TANK .FILL .LVL

LIMIT: .4 .TO .17 .LBS .

PRESS .START ./ .YES .TO .SAVE

3 . .Use .the .arrow .keys .to .enter .a .value .between .4 .lbs . .

and .17 .lbs ., .and .press .START / YES.

Figure 8

O-rings

Figure 9

Check for Leaks

Check .the .unit .for .leaks .every .three .months, .or .as .

specified .by .law .in .your .jurisdiction . .
1 . .Turn .off .MAIN POWER, .and .disconnect .the .power .

cord .from .the .outlet .

2 . .Open .the .rear .door; .remove .top .cover .and .front .panel .
3 . .Use .a .leak .detector .to .probe .all .connections .for .

refrigerant .leaks . .Tighten .fittings .if .a .leak .is .indicated .

4 . .Reassemble .the .body .panels, .and .close .the .rear .door .

Inspect the unit periodically for leaks.

The manufacturer does not reimburse

for lost refrigerant.