beautypg.com

Thermostat specifications, Operational mode chart – Robertshaw RS6320 User Manual

Page 14

background image

14

To unlock the buttons:

1. Push and hold the

and

buttons for 5 seconds until the

request for password is displayed.

2. Enter the digits for the password by pressing the

and

buttons. Press the

to move to the next digit. Press

to

move back.

3. When the correct password is set, wait for 5 seconds to unlock

the system.

4. If the wrong password is entered the display will flash -- for 5

seconds then return to normal.

Once the security has been disabled, a password needs to be
re-created to protect the settings.

Thermostat Specifications

Operating Voltage

18-30V AC

Maximum Load Current

1 Amp Max per Output Terminal

4 Amp Total Load

Output Type

Latching Relays

Batteries

2 AA Alkaline in Series

Battery Life

2 Years Typical

Ambient Operating Temperature

14 °F (-10 °C) to 122 °F (50 °C)

Storage Temperature

-4 °F (-20 °C) to 140 °F (60 °C)

Operational Mode Chart:

Demand

Conventional

(Non-HP)

Heat Pump

(HP) Elec

Heat Pump

(HP) Gas

First Stage Heat

W1 + G*

Y1 + G + B

Y1 + G + B

Second Stage Heat

W1 + W2 + G*

Y1 + Y2 + G + B

or

Y1 + W2 + G + B

Y1 + Y2 + G + B

or

Y1 + W2 + G + B

Third Stage Heat

N/A

Y1 + Y2 + E +

G + B

or

Y1 + W2 + E +

G + B

E + B

Emergency Heat

N/A

Y1 + G + O

Y1 + G + O

First Stage Cool

Y1 + G

Y1 + Y2 + G + O

Y1 + Y2 + G + O

Second Stage Cool

Y1 + Y2 + G

E + G

E

* G: G is off for Gas, on for Elec

This manual is related to the following products: