ITEM
Parallel Blade
Rectangular Damper
POWER REQUIREMENTS
24 VAC actuator
AMBIENT RATINGS
0˚F to 120˚F (-18˚C to 49˚C)
LEAKAGE
Low leakage damper
STATIC PRESSURE RATING
1.2” WG
DIMENSIONS
6” wide x 6” high to 36” wide x
36” high (15 cm wide x 15 cm high
to 91 cm wide x 91 cm high)
WEIGHT
3 lb. to 27.5 lb. (1.4 kg to 27.5 kg)
WIRING
#18 gauge thermostat wire
ACTUATORS
2-wire, 2 position, spring return
(55 in-oz)
3-wire, 2 position, power open-power
closed (150 in-oz)
FRAME
6063 T5 extruded aluminum
4” channel frame
BLADES
4” wide 6063 T5 extruded aluminum
airfoil design
6” wide 6063 T5 extruded aluminum
airfoil design
PIVOT PINS
1/2” diameter octagonal extruded
aluminum
LINKAGE
Concealed side linkage
BEARINGS
Nylon
MOUNTING PLATE
18-gauge galvanized steel mounting
plate 6” wide
ROBERTSHAW PANELS
• Classic panel: up to 2 zones
2701-006
up to 3 zones
2701-001
• Deluxe panel: up to 7 zones
2701-002
• Premier panel: up to 19 zones 2702-001
ROBERTSHAW DAMPERS
• Rectangular motorized zone dampers
• Round motorized zone dampers
• Bypass non-electric zone dampers
ROBERTSHAW THERMOSTATS
• Programmable thermostats
• Digital non-programmable thermostats
• Mechanical thermostats
Design Specifications
Robertshaw
®
Zone
Control Systems
Distributed by:
PARALLEL BLADE
RECTANGULAR
ZONE DAMPERS
ORDER NUMBER
Ex. DAOP0820E2
TYPE
Parallel Blade
Rectangular Damper
NON-ACTUATOR SIDE
08 (6” to 36”)
ACTUATOR SIDE
20 (6” to 36”)
ACTUATOR TYPE
E2 (2-wire control)
E3 (3-wire control)
FAIL SAFE
Blank (normally open)
NC (normally closed)
Ordering Information
•
•
•
•
•
•
•
•
Climate Controls Americas
515 South Promenade Avenue
Corona California 92879-1736 USA
Telephone +1 800 951 5526 Facsimile +1 630 260 7299
[email protected]
Technical Service Telephone +1 800 445 8299
Technical Service Facsimile +1 630 260 7243
[email protected]
www.icca.invensys.com