Step 4: Customizing the Thermostat

Settings

System
Cool: The thermostat controls the cooling.
Off:

The heating and cooling systems are off.

Fan

Auto: Equipment controls the fan.
On:

The fan operates continuously.

Temperature Differential

The temperature differential is factory set at 1.0°F (.5°C). This means that
whenever the room temperature changes by one degree Fahrenheit
from the temperature setting, the system will turn on. If the system turns
on too often, increase the temperature differential.

Changing Fahrenheit (°F) to Celsius (°C),
the Temperature Differential, and
the Filter Monitor

1. The thermostat is preset to display the

temperature in degrees Fahrenheit (US
models) or degrees Celsius (Canadian
models). The temperature display can be
changed. Press and hold both the

and

buttons for three seconds. The display will flash either an F

or C. Release buttons. Press the

or

button to switch the display.

2. Wait five seconds or press

and the display will switch to the

differential setting.

3. The display will read diFF. The tempera-

ture differential is factory set at 1.0°F
(0.5°C). Press the

or

button to adjust

the differential up or down.

4. Wait five seconds or press

and the

display will switch to the
filter monitor setting.

5. CHECK FILTER and the length of hours for

the filter monitor will be displayed.

6. Use the

or

to adjust the filter timer

from 0 (OFF) to 9900 hours. NOTE: The
filter timer is based on equipment run
time. Select the length of time based on
the recommended service interval for
your filter.

7. Press the

to return to normal operation.