Terminal designations specifications, Architectural / engineering specification, Shipping information – Robertshaw 300-229 User Manual
Page 2: Deluxe programmable thermostat
Terminal Designations
Specifications
Electrical rating: 24 Volt AC (20-30 VAC)
0.05 amp - 0.75 amp per output
3 Amp total maximum load (all terminals combined)
Temperature control range:
Heating: 40° - 88°F (6° - 30°C)
Cooling: 60° - 108°F (16° - 40°C)
Accuracy: +/-1°F at 68°F (0.5°C at 20°C)
Auto Changeover deadband: 2°F (1°C)
Temporary temperature override: 3 hours maximum
Remote sensor capable: Up to 6 remote sensors
System configuration: Multi-stage gas, oil or electric heating/cooling
systems (up to 2 stages of heat, 2 stages of cool).
Other Multi Stage Gas / Electric
Heat / Cool Thermostats
9515: Digital, Non-Programmable
9615: Programmable, 7 Day
9710: Deluxe Programmable, 7 Day
300-203: Digital, Non-Programmable
Architectural / Engineering
Specification
The thermostat shall be a Robertshaw Model 300-229 or equivalent. The
thermostat shall have seven-day programmability with up to 4 time/temperature
changes per day. The thermostat will allow temporary temperature override
for a maximum of 3 hours or the next setpoint time, whichever occurs first.
The thermostat shall allow the user to program the system fan separately for
continuous or automatic operation for each of the 4 time setpoints per day
to meet local application and code requirements.
It shall be capable of operating with standard 24 VAC 2 stages of heat and
2 stages of cooling for gas, oil or electric heating and/or electric heating /cooling
systems. The thermostat shall have an electrical rating of 0.75 amp maximum load
per terminal, 3 amp total maximum load for all terminals combined. The
thermostat shall have relay outputs with standard 24 VAC control circuits and
be equipped with back-up circuitry to prevent loss of programming in memory
during power outages.
The thermostat shall have automatic changeover capability to allow the thermostat
to determine whether the heating or cooling program should be used to control
room temperature.
The thermostat shall be equipped with trouble LED’s for selectable programmed
operation. The thermostat will have an auxiliary relay coil which energizes during
the occupied periods and de-energizes during unoccupied periods.
The keypad and case shall have an integral lock to prevent tampering and/or
the altering of the program. The switching voltage shall be independent of the
heating and cooling system transformer. The thermostat will provide remote sensor
capability for up to six temperature sensors (including main thermostat sensor).
The thermostat shall be equipped with a 5-minute delay on break for compressor
short cycle protection during cooling operation to prevent compressor damage.
300-229
Shipping Information
Indiv. Ctn. Dim.: 4.75” x 6” x 1.75”
Master Ctn. Qty.: 20
Master Ctn. Dim.: 10" x 6.25” x 17.5"
Master Ctn. Cu. Ft.: .64
Master Ctn. Wt.: 15 lbs.
Max. Pallet Qty.: 1120
Max. Pallet Wt.: 860 lbs.
Item 10-528 & 10-529 Remote Sensor
Indiv. Ctn. Dim.: 4.75” x 6” x 1.75”
Master Ctn. Qty.: 40
Master Ctn. Dim.: 10" x 12.5” x 17.5"
Master Ctn. Cu. Ft.: 1.28
Master Ctn. Wt.: 14 lbs.
W2
Heating
Relay
(2nd Stage)
W1
Heating
Relay
Y2
Cooling
Relay
(2nd Stage)
Y1
G
Fan
Relay
Cooling
Relay
R
24V
24V(C)
O
B
24 VAC
Equipment
Transformer
Independent
Switching
Voltage
Cool Active
Reversing
Valve
24 VAC
Equipment
Common
Heat Active
Reversing
Valve
Distributed by:
DELUXE
PROGRAMMABLE
THERMOSTAT
LED1
Selectable
Function
Indication
RS2
LED2
RS1
RS+V
Outdoor/Indoor
Sensor
NO
COM
NC
Occupancy Relay
Coil, De-energize
during night event
Optional Remote Sensors:
INDOOR OUTDOOR
10-528 10-529
White-Rodgers Company*
1F97
Honeywell, Inc.*
T7300D2007
* Verify specific application requirements before substitution.
THE ROBERTSHAW
300-229
REPLACES:
®
Climate Controls Americas
515 South Promenade Avenue
Corona California 92879-1736 USA
Telephone +1 800 304 6563 Facsimile +1 800 426 0804
Outside the USA +1 909 734 2600
www.icca.invensys.com
©2003 Climate Controls Americas 6/03 - #150-1556B