LumaStream Trinity PERMANENT User Manual
Page 9

Document: 66APPMAN Rev: H
24 of 32
11.3 Analog Interface Specifications
The TRINITY ANALOG is compatible with commercial dimming panels and
wall box dimmer products meeting IEC 60929(AnnexE) requirements.
The TRINITY ANALOG has been tested with the following 0-10 Vdc Analog
wall box dimmer products:
·
HUNT PS LED series
·
LEVITON DECORA IP710_DL
Additional Analog 0-10 Vdc dimmer products may also be compatible with
the TRINITY ANALOG. Consult LumaStream for compatibility
11.4 Analog Interface Cabling and Connections
In the end use application, proper separation between the class 2 control
wiring from the analog 0-10 Vdc interface and AC mains must be
observed in accordance with the applicable safety standards and/or
NEC/CEC requirements.
The total run length of the 0-10Vdc control wiring (purple and grey) #18
AWG should not exceed 500 feet (150 meters). In situations where the
control wiring is greater than 500 feet or electrical noise is present,
shielded twisted pair cabling should be used.
CAUTION
RISK OF DAMAGE:
DO NOT connect AC input of power unit to a phase cut dimmer or dim-
ming panel It will cause internal damage to the power unit
Document: 66APPMAN Rev: H
9 of 32
5.0
INSTALLATION GUIDELINES AND SAFETY
REQUIREMENTS
This power unit has been evaluated to the requirements for:
UL 60950-1 2nd Edition - Information Technology Equipment-
Safety Part 1: General Requirements
CSA C22.2 No. 60950-1-03, 2nd Edition - Information Technology
Equipment-Safety Part 1: General Requirements
IEC 60950-1:2005 Second Edition
UL8750 1
st
Edition: LED Light Equipment for Use in Lighting Prod-
ucts
5.1 ELECTRICAL REQUIREMENTS
This power unit is intended for connection to a 20A branch circuit
and an appropriate disconnect device shall be provided as part of
the building installation.
All secondary output circuits are SELV, limited power source (LPS)
and Class 2.
5.2 MOUNTING AND ENVIRONMENTAL REQUIREMENTS
This power unit is limited to fixed plenum or non-plenum locations.
Only output cables marked with “CMP” may be installed in plenum
locations.
This power unit is rated for dry locations only.
The power unit is intended for use in a nonconductive pollution
environment only.
This power unit is rated for operation at a maximum ambient tem-
perature of 40 ºC.
Allow sufficient spacing around heatsink extrusion fins for convec-
tion air flow.
Do not block ventilation openings.
WARNING
RISK OF FIRE OR ELECTRIC SHOCK:
Shut OFF power at fuse box or circuit breaker before installation
Turn power OFF before inspection or removal
Properly ground power unit to main protective earthing
Follow all NEC/CEC, local electrical code requirements for installation
Do not remove enclosure cover. No serviceable parts inside
Do not connect Analog Interface to class 1 circuits
To reduce the risk of fire or electric shock, do not interconnect output
terminations