LumaStream Trinity PERMANENT User Manual
Page 7

Document: 66APPMAN Rev: H
26 of 32
Note: This wiring configuration provides simultaneous dimming control
for all zones 1,2,3,4 with a commercial dimming interface comprising (1)
0-10Vdc control signal.
11.6 INSTALLATION EXAMPLES
(1) TRINITY ANALOG, (1) COMMERCIAL DIMMING PANEL
WITH (1)
Document: 66APPMAN Rev: H
7 of 32
Table 10
TRINITY Multi-Zone Analog Model Options
Model #
# of
Channels
Drive
Current
Output Voltage
Range (under
load Conditions)
Maximum # of
LEDs per
Channel
(typical)
70-12-0350-12Z-PI
12
350 mA
12 to 47 Vdc
4 to 12
70-09-0500-12Z-PI
9
500 mA
12 to 47 Vdc
4 to 12
66-12-0700-12Z-PI
12
700 mA
6 to 27 Vdc
2 to 8
66-09-1000-12Z-PI
9
1000mA
6 to 27 Vdc
2 to 8
Table 11
Multi-Zone Analog Interface Specifications
Control Method
Analog 0-10Vdc
IEC 60929 Annex E Out-
puts 0.5mA maximum
Or
Variable 0-10Vdc Voltage
Source
Class 2 outputs
Master Control:
Simultaneous control of all
output channels
Zonal Control:
Independent control of up to 12
channels
Loss of Analog
Input Signal
Outputs will go to 100% light intensity in less than 1 second
Connection Method
UL recognized cage clamp connector
14 AWG to 28 AWG wiring
Electrical Isolation
Master, Zone 1 to Zone 12 outputs
electrically isolated from earth ground