LumaStream Trinity PERMANENT User Manual
Page 16

Document: 66APPMAN Rev: H
16 of 32
10.2 DMX LED Status Indicator
Power Indicator-Green LED will turn off if no power is detected.
DMX Active– Yellow LED will flash at a constant rate if active DMX
packets are received for DMX address set to 1-512.
DMX Inactive– Yellow LED will flash and then pause off at continuous
rate if no DMX packet received
DMX Address Change after power up– Yellow LED will remain on (no
flashing) if address has changed by rotary switch after unit powered
up. Yellow LED will resume flashing at constant rate within 2 seconds
after new address confirmed.
DMX Address set to 513-542– Yellow LED remains on with no
flashing for built in test routines
Output Channels 10,11,12
Output Channels 1,2,3
Output Channels 7,8,9
Output Channels 4,5,6
P
ow
er
I
nd
ic
at
or
D
MX
A
ct
iv
e
In
dic
at
or
Document: 66APPMAN Rev: H
17 of 32
10.3 DMX Interface Connections
The table below references required wiring connections for RJ45 like (IEC
60603-7 8 Position) Modular Connectors.
DMX Connector Pinouts
DMX Connections
Pin (Wire) #
Wire Color
DMX512 Connection
1
white/orange
Data 1+
2
orange
Data 1-
3
white/green
Data 2+ (optional)
4
green
Data 2- (optional)
5
blue
Not assigned
6
white/blue
Not assigned
7
white/brown
Data link common (common reference)
for data 1 (0 V)
8
brown
Data link common (common reference)
for data 2 (0 V)
Note 1: Pin Numbering and color in accordance with ANSI/TIA/EIA-
568 scheme T568B
Note 2: Pin 8 should be wired as signal common even if pins 3 and 4
are NOT wired so that both conductors 7 and 8 are at equal poten-
tial
Note 3: TRINITY DMX utilizes pins 1,2 and 7 only
WARNING: Accidental Connection to non-DMX equipment may re-
sult in damage to equipment. Pins 4 and 5 may carry voltages out-
side the EIA-485 range in telecom applications (e.g. telephone ring-
ing). Pins 4 and 7 may carry voltages outside the EIA-485 range in
other applications.