10.4 DMX Cabling
The DMX cable should meet EIA485 requirements. The characteristics
for this cable include low capacitance, twisted pair, shielded, and
designed for high speed data.
Twisted pair Ethernet cabling referred to as Category 5 cable may be
a cabling option upon successful evaluation in the end use application.
In the end use application, proper separation between control wiring
from the DMX interface and AC mains must be observed in
accordance with the applicable safety standards and/or NEC/CEC
requirements.
The maximum permissible cable length between DMX Controller
(transmitter) and last TRINITY is 1000 feet (300 meters). A DMX split-
ter (preferably isolated) may be required to extend the cable length.
10.5 DMX Loop Thru, Addressing and Termination Requirements
DMX Controller
DMX Rotary Switches
120 ohm
Termination
Document: 66APPMAN Rev: H
15 of 32
10.1 TRINITY DMX Typical Wiring Diagram
DMX512
CONTROLLER
DMX
IN
DMX
OUT
DMX
IN
DMX
OUT
R
B
G
JU
N
C
T
IO
N
B
O
X
JU
N
C
T
IO
N
B
O
X
R
B
G
R
B
G
R
B
G
R
B
G
R
B
G
R
B
G
R
B
G
Channels
10,11,12
Channels
7,8,9
Channels
4,5,6
Channels
1,2,3
RJ45 CABLE
RJ45 CABLE
120 OHM
TERMINATION
UP TO 64 TRINITY UNITS
MAY BE DAISY CHAINED
LAST UNIT IN CHAIN
MUST HAVE TERMINATING RESISTOR