LumaStream Trinity PERMANENT User Manual
Page 4

Document: 66APPMAN Rev: H
4 of 32
Table 1
Input Specifications
Rated Input Voltage
And Frequency
115 to 277
47-63
Vac
Hz
Rated Input Current
A
A
66-xx-yyyy-zzz-n models
2.7-1.1
70-xx-yyyy-zzz-n models
2.4-1.0
Power Factor
EN61000-3-2
@ 115 Vac, 100% load
0.97
W/VA
min
Input Current Total
Harmonic Distortion
@ 115 Vac 100% load
13
% max
Table 2
Output Specifications
Rated Output
Power
66-xx-yyyy-xxx-n models
70-xx-yyyy-xxx-n models
@ 40 °C ambient
243
226
W max
Efficiency
100% load @
115 Vac input
87
%
Turn on delay
Time required for
stabilization of all
Outputs
2
sec
typical
Output Current
Tolerance
+/-5 % of nominal
Table 4
Environmental Specifications
Location Rating
Dry
Operating Ambient Temperature
-20ºC to +40ºC
Cold Start Temperature
-20ºC
Storage Ambient Temperature
-40ºC to 80ºC
Relative Humidity
5% to 95% noncondensing
MTBF (MIL HDBK-217F)
(12 channel)
>60,000 hours @ 40ºC
>97,000 hours @ 25ºC
Table 3
Safety and EMI/EMC Specifications
Agency Approvals
See Section 5.0
Conducted & Radiated Emissions
ICES-003
FCC Title 47, Part 15 Class A
EMC
EN61547-General Lighting
1.1 SPECIFICATIONS
Document: 66APPMAN Rev: H
29 of 32
12.0
0-10 Vdc MULTI-ZONE ANALOG INTERFACE
12.1 LED Status Indicator
Analog Dimming Indicator-Green LED will be in one of the following
states when the unit is powered:
Flashing Fast - Master Dimming input is at full On (100%)
Flashing Slow - Master Dimming input fully dimmed (0%)
Steady State - Green LED will vary in intensity proportionally to
master 0-10 Vdc control signal for intensity levels between 0%
and 100%.
Zone 10, 11, 12
Output
Zone 1,2,3
Output
Zone 7,8,9
Output
Zone 4,5,6
Output
Zone
Dimming Inter-
face Connections
Ana
log D
im
m
ing
Ind
ic
a
to
r
Master Dimming
Interface
Connection