FIREPOWER Firefinder XLS User Manual

Page 4

background image

s

Industry, Inc.

Building Technologies Division

Model HLIM does not occupy a device address on the Model

DLC circuit, and does not require programming. Up to 15

Model HLIM modules may be installed on each Model

DLC loop.

HCP Control Point Module

HCP
Model HCP provides an intelligent control point for the

FireFinder XLS Control Panel. Model HCP can be

programmed as an independent, remotely located tele-

phone zone, speaker zone or notification appliance circuit.
Model HCP is designed to be used with the Siemens Fire

Safety Notification-Appliance Circuits product line.
Model HCP communicates through the Model DLC analog

loop, and can be wired either Class A (Style Z) or Class B

(Style Y). The 24 VDC power input comes from either the

control panel or from any UL listed power-limited,

auxiliary-power supply.

CRC-6 Controllable Relay Card

CRC-6 Controllable Relay Card
The Controllable Relay Card (Model CRC-6) is used with

the FireFinder XLS FACP. Model CRC-6 is designed to

provide auxiliary control of building functions, such as:

door-holder release, elevator capture, smoke control, lock

release, etc. Model CRC-6 plugs into one (1) slot in the

Model CC-5 or Model CC-2 card cage. Model CRC-6

provides six (6), fully programmable relays. Each relay
contains one (1) set of SPDT contacts rated at 4 Amps 30 VDC

/ 120 VAC resistive and 3.5 amps 120 VAC inductive (0.6

P.F.)

SIM-16 Supervised Input Module

SIM-16 Supervised Input Module
The Supervised input Module (Model SIM-16) is a

remotely located, general-purpose input module. Model

SIM-16 provides 16 input circuits for remote system
monitoring. Each input can be individually programmed

as supervised (dry-contact only) or unsupervised (general-

purpose input.) Model SIM-16 has two (2) Form C relays.

The relays and inputs are programmed using the Zeus

system software-programming tool.

CDC-4 Conventional Detector Card

CDC-4
The Conventional Detector Card (Model CDC-4) is used to

monitor Siemens Fire Safety conventional detectors on the

FireFinder XLS system. Model CDC-4 can be used in

applications where conventional detectors are more suited

than addressable detectors, such as hallways or large

meeting rooms. Also, Model CDC-4 can be used to

upgrade Siemens conventional fire-alarm panels to the

FireFinder XLS system without requiring detector

replacement.

CC-2 Card Cage-2 Slots CC-5 Card Cage-5 Slots

CC-5 / CC-2 Card Cages
The Models CC-5 / CC-2 card cages provide the physical

mounting location and all wiring connection points for all

fire-and-voice system options cards for the FireFinder XLS

system. Model CC-5 has five (5) slots, while Model CC-2

has two (2) slots.