beautypg.com

FIREPOWER CP35 User Manual

Fire safety, Operating instructions, Model cp-35 control panel

background image

PIN 315-084881-5

*When this feature is incorporated in the system.

Fire Safety

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

These instructions should be framed and located adjacent to the control unit for ready reference.

Your local Siemens Building Technologies, Inc. Authorized Service Representative is:
Name ______________________________________________
Tel. No. _____________________________________________

OPERATION

In normal standby operation, all switches should be in normal

position. The system power lamp should be on and the system

alarm, system trouble lamps, zone alarm, zone trouble, audible

signal circuit trouble LED indicators, and all other indicators should

be off.

When System Alarm Sounds

1. If system is used for fire detection, follow the response plan

approved by the authority having jurisdiction. Check that every one

is accounted for. Then, notify the Fire Department. (If the system

is connected to the Fire Department or a Central Station, this is

done automatically by the control equipment.) Keep in mind that

the Fire Department or Central Station should be notified when

resetting the system.
2. Audible device circuits associated with the silenceable alarm

output may be silenced by momentary operation of the ALARM

SILENCE switch. Subsequent alarm conditions from another zone

will cause the above audibles to sound again. DO NOT RESET

THE SYSTEM. The zone LEDs will indicate the zone in which the

alarming device is located. Locate the device initiating the alarm.

This device will have its base lamp* on.
3. When the cause of the alarm has been located and corrected,

reset the system by moving the RESET/LAMP TEST switch to

RESET position for a minimum of 5 seconds. Reset all other

switches that have been operated. Notify the Fire Department (or

Central Station) that the system is being reset.

When a Trouble Condition Develops

1. The system trouble lamp and horn are activated. Call your

authorized Siemens Building Technologies, Inc. Service Represen-

tative. The trouble should be diagnosed and repaired immediately.
2. The trouble buzzer may be silenced by moving the TROUBLE

SILENCE switch to the SILENCE position. The trouble lamp will

remain illuminated.

MAINTENANCE

To insure proper and reliable operation, the following inspection

and testing schedule is recommended:

Every Six Months

1. Inspect all ionization detector heads for dust accumulations, and

when excessive, contact your authorized Siemens Building Tech-

nologies, Inc. Service Representative or factory for service.

2. Activate a detector or alarm initiating device. Check that the base

lamp lights* and that proper alarm and zone indications are given

by the control panel. An ionization or photoelectric detector may

be activated by blowing smoke into it. A thermal detector may be

activated by an electric “heat gun.” A flame detector may be

activated by holding a lighted match slightly below it.

IMPORTANT: If the system is connected to the Fire

Department, or actuates an external system (fire extin-

guishing, etc.), move disconnect switches* to OFF

position to prevent actuation. Be sure to reconnect at

completion of inspection. Notify facility personnel that

a system test is being performed so that any alarm

soundings can be ignored during the test period.

3. Check operation of each detector/alarm initiating device on all

circuits. Measure the sensitivity of each ionization detector with a

sensitivity checker (when applicable).
4. Check the supervisory circuits by operating the RESET/ LAMP

TEST switch to the RESET position. In this position, all visual

indicators on the control panel should be lit and the trouble horn

should sound.

Periodically Testing the System

1. The system should be tested at regular intervals to insure its

operational reliability and optimum performance. To test the sys-

tem, activate a detector/alarm initiating device.
Check that all audible devices sound, that the system alarm lamp

illuminates, and that the audible devices can be silenced.* Check

that the proper zone lamp responds.
2. Reset the system. Check that the system trouble lamp LEDs and

horn and all zone lamps* are actuated when the reset switch is

moved momentarily to the RESET position.
3. Retum all switches to normal position.
4. If a disconnect switch is incorporated, and if the system is

connected to a fire department, central station, or has external

devices connected to it (fans, smoke door holders, fire extin-

guishing systems, etc.) which are operated by the alarm controlled

contacts, this equipment may be isolated from the alarm circuit

during a test by moving the respective disconnect switch(es) to the

DISCONNECT position. Operation of this switch prior to tests lights

the trouble lamp so that the switch will not be left in the DISCON-

NECT position inadvertently.

Model CP-35 Control Panel

Operating Instructions