Specifications and Dimensions
Horizontal SteamPacs
Specifications – Fulton Horizontal SteamPacs from 70 to 350 HP
Models FT
070XH
100XH
150XH
180XH
200XH
250XH
300XH
350XH
Steam Output*
LB/HR
KG/HR
2,415
1,096
3,450
1.565
5,175
2,347
6,210
2,817
6,900
3,130
8,625
3,912
10,350
4,695
12,075
5,477
Input
BTU/HR (1000)
KCAL/HR (1000)
2,343
590
3,347
843
5,021
1,265
6,025
1,518
6,694
1,687
8,368
2,108
10,041
2,530
11,715
2,952
Flow Rate
GPM
M3/HR
160
37
228
52
342
78
411
94
456
104
570
130
684
156
798
182
*From and at 212
o
F (100
o
C). Steam Output is based in a minimum thermal fluid temperature of 425
o
F (218
o
C)
Dimensions – Fulton Horizontal SteamPacs from 70 to 350 HP
Models FT
070XH
100XH
150XH
180XH
200XH
250XH
300XH
350XH
A. Width
IN
MM
68
1,727
80
2,032
80
2,032
80
2,032
96
2,438
96
2,438
96
2,438
96
2,438
B. Length
IN
MM
107
2,718
117
2,972
117
2,972
132
3,353
150
3,810
150
3,810
150
3,810
160
3,810
C. Height
IN
MM
75
1,905
110
2,794
110
2,794
110
2,794
112
2,845
112
2,845
112
2,845
112
2,845
All dimensions are based on 550oF thermal fluid temperature and are subject to change based on