Page 16

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201
Page 16
2. The high limit pressure control must be manually reset by depressing the
plunger located on top of the control.
8. Ventilation
a) Ventilation in the room must be sufficient to maintain a building temperature of 100°F or
less.
9. Feedwater
a) In its readily available form, water is a corrosive chemical solution having dissolved and
suspended solids and it is therefore, essential that feed water for any steam generating
plant be conditioned prior to use. Specialists in water treatment should always be
consulted.
b) Just with any other type of steam boiler, the generator must be fed with clean soft water
free from calcium and magnesium salts, organic compounds and corrosive reagents. See
the table below for upper limits of water characteristics for the steam generator use.
10. Recommended Water Conditions for Boilers/Unfired Steam Generators
a) Following are recommendations for feed water and boiler water. Contact your local water
treatment professional for testing and treatment recommendations. It is very important
that a strict water treatment program be followed.
b) It is critical that the boiler pH follow the attached schedule whenever water is in the boiler.
Solids that enter in with the feed water will concentrate in the boiler. A regular schedule of
boiler blowdown must be maintained to prevent high solid concentrations from corroding
the vessel or forming deposits.