Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201
Page 50
deposits occur, have the water analyzed and treated by
a reliable chemical treatment company. Remove any
mineral deposits from pump parts.
4. Worn bearings. Replace.
5. Pump cavitation. High water temperatures
or a suction line restriction, such as a clogged strainer,
will cause cavitation. Any restriction must be corrected
immediately or severe pump damage will result.
3. Problem: Receiver
overflows
constantly.
Check:
1. Make-up valve seat worn, not sealing tight.
Replace valve.
2. Make-up valve float waterlogged or disconnected.
Replace.
3. Lower the level of make-up water to allow
more tank volume for condensate.
4. Problem:
Some Common Causes of Motor Failure.
Check:
1. Tripped starter overload. Reset and check
motor and pump for proper operation.
2. Improper power supply. Check voltage and
motor nameplate data.
3. Incorrect connections. Check wiring diagram.
4. Mechanical failure. Check for free rotation
and examine bearings.
5. Short-circuited windings. Indicated by blown
fuse or failure to start. Motor must be replaced.
6. Overload. Check pump for proper operation and free
rotation.
7. One phase open in three-phase circuit. Check power
supply lines.
5. Problem:
Starter overload tripped.
Check: