Section 2 – Installation
1.
Introduction
a) This manual is provided as a guide to the correct operation and maintenance of your
unfired steam generator, and should be permanently available to the staff responsible for
the operation and maintenance of the unfired steam generator. These instructions must
not be considered as a complete code of practice, nor should they replace existing codes
or standards that may be applicable.
b) In the event that you require after sales service, Fulton Thermal Corporation has a
complete staff of field service technicians, and spare parts are available direct from the
factory. Should you require additional information or assistance on the operation and
maintenance of your unfired steam generator, please contact the Fulton service
department at (315) 298-7148 or contact your local Fulton Representative.
2. Placement
a) Proper placement of your unfired steam generator is essential. Attention paid to the
following points will save a great deal of difficulty in the future. Correct placement is the
first step to trouble free installation, operation and maintenance.
3. Transport
a) Fulton SteamPacs are skid mounted. Rollers should be placed beneath the frame of the
skid or the fork lift holes in the bottom of the skid may be utilized for positioning in the
installation area.
4. Location
1. Authorities with jurisdiction over any national, local or insurance codes should be
consulted prior to installation to assure compliance.
2. The unfired steam generator should be located as close as possible to the steam users in
order to keep condensation & pressure drop to a minimum.
3. A level, hard surface of non-combustible material is required as a suitable base for
mounting the unit. It is suggested that a 4” containment curb be installed completely
around the unit. In the event of a spill of thermal fluid, the curb will help contain the fluid.
5. Access
1. Access around the unfired steam generator should be provided to facilitate maintenance.
Place the SteamPac with clearances to unprotected combustible materials including
plaster or combustible supports not less than the clearances listed in the table below.