Operation, Emergency shut off procedures, Starting boiler after prolonged shutdown – Fulton Caliber (CAL) Condensing Hydronic Boiler User Manual
Page 42

© The Fulton Companies 2014
OPERATION
CAL-IOM-2014-0129
SECTION 3
3-8
2. Close all manual gas valves.
3. Turn
off electrical power.
Emergency Shut Off Procedures
The main gas cock should be closed immediately. If
overheating occurs or the gas supply fails to shut off , do not
turn off or disconnect the electrical supply to the pump.
Instead, shut off the gas supply at a location external to the
boiler.
Shutting the Boiler Down for an Extended Period
of Time
If the boiler is to be shut off for a period greater than 3
months:
1. Perform normal shut down procedure, see above.
2. Isolate water supply and fl ow circuit from boiler.
3. Drain
boiler.
4. Disconnect electrical supply.
Starting Boiler After Prolonged Shutdown
Perform initial start up procedures as described in this
manual.