Installation – Fulton Caliber (CAL) Condensing Hydronic Boiler User Manual
Page 10

© The Fulton Companies 2014
INSTALLATION
CAL-IOM-2014-0129
SECTION 2
2-4
TABLE 1 - OPERATING REQUIREMENTS (SEE TABLE NOTES ON PAGE 2-5)
Caliber Model Size
300
500
750
850
Input (BTU/Hr)
300,000
500,000
750,000
850,000
Output (BTU/Hr)
283,500
472,500
708,750
803,250
Natural Gas Consumption (ft3/hr)
297
495
743
842
Propane Consumption**(ft3/hr)
120
200
300
340
Gas Supply Pressure Minimum
Maximum
4.0
14
4.0
14
4.0
14
4.0
14
Dry Weight LB
KG
500
630
719
729
227
286
326
331
Operating Weight LB
KG
518
662
757
772
235
300
343
350
Control Voltage (V/Hz/Ph)
120/60/1
Blower Voltage (V/Hz/Ph)
120/60/1
X. Electrical Connection*
120/60/1
Y. Condensate Drain Connection* IN
MM
0.75
.075
0.75
0.75
19
19
19
19
Amp Draw
2.1
3.6
3.6
3.6
I. Gas Connection* IN
MM
.75
1
1.25
1.25
19.0
25.4
31.75
31.75
G. Water Inlet/Outlet Connection* IN
MM
1.25
1.5
2
2
31.75
38.1
50.8
50.8
J. Flue Connection (ID)* IN
MM
4.25
4.25
5.875
5.875
108
108
149
149
H. Air Intake Connection***(OD) IN
MM
4.5
4.5
4.5
4.5
114
114
114
114
A. Boiler Width (including feet)* IN
MM
34.5
34.5
34.5
34.5
876
876
876
876
B. Boiler Height* IN
MM
51.6
51.6
51.6
51.6
1310
1310
1310
1310
C. Boiler Depth (Cabinet)* IN
MM
31.25
44
57.25
57.25
793
1117
1454
1454