Table 8 general specifications, Table 9 fault code/ audible alarm – PROLiNK IPS5000 User Manual

Page 17

background image

- 15 -

Table 8 General Specifications

Safety Certification

CE(EN60950)

EMI Classification

EN62040-2, CLASS A

Operating Temperature Range

0°C to 45°C

Storage temperature

-15°C ~ 60°C

Altitude, operational

Elevation: 0 ~ 1500 Meters

Relative humidity

5% to 95% non-condensing

Audible Noise

60dB max

Cooling

Forced air, variable speed fan

Dimension

350mm(W)*110mm(H)*407mm(D)

Net Weight

9KG

Table 9 Fault code/ Audible alarm

Restart

Fault

Code

Protect

Function

Active

Mode

Condition

Warning

(O/P=ON)

Fault

(O/P=OFF) Operate Condition

--

Low DC
Voltage
Alarm

Inverter

DC voltageDC Alarm

1beep/2s -- --

--

0

Low DC
Voltage
Protection

Inverter

DC
VoltageDC Shut-down

--

Beep

continuous

Auto

Mains is normal

1

Over
Charge
Protection

Line

DC
Voltage>High
DC input
Shut-down

Beep

continuous

-- Manual

--

1

Over
Voltage
Protection

Standby

DC
Voltage>High
DC input
Shut-down

--

Beep

continuous

Auto

DC

Voltage

DC input

Shut-down

Recovery

110%~150%
load

1beep/0.5s,and

continuous 10s

Beep

continuous

Manual --

2

Over Load
Protection

Line/

Inverter

>150% load

1beep/0.5s,and

continuous 5s

Beep

continuous

Manual --

3

Output
Short Circuit
Protection

Inverter

Output
Voltage<20Vrms

--

Beep

continuous

Manual --

4

Fan Fault
Protection

Line/

Inverter

Fan Locked
Fan Defected

2beep/2s,and

continuous

1min

Beep

continuous

Manual --

5

Over Temp
Protection

Line/

Inverter

HEAT SINK
Temp≥100℃

--

Beep

continuous

Auto

HEAT SINK

Temp≤ 55℃

6

Back-EMF
Protection

Standby

Reverse input
and output

--

Beep

continuous

Manual --

9

Output
Abnormal

Inverter

(Output Voltage

<170Vrms and

output current

under 32Arms)

or Output

Voltage

>280Vrms

--

Beep

continuous

Manual --